99
ENG
Web server
g0300122EN rel. 1.0 - 01.12.2021
Type
Add.
Occ.
Variable name
Description
Def.
Min
Max
UoM
Access
HoldingRegister 128
2
DilDrainCfg.PeriodicDilDrain-
Thrsh
Set number of hours between two periodic drain
to dilute cycles if micro-fi lling mode active
10
1
24
[h]
RW
HoldingRegister 130
1
DilDrainCfg.DailySched[1].
Start_h
Drain to dilute - Daily scheduler (Monday) -
hours
23
0
23
[h]
RW
HoldingRegister 131
1
DilDrainCfg.DailySched[1].
Start_min
Drain to dilute - Daily scheduler (Monday) -
minutes
0
0
59
[min]
RW
HoldingRegister 132
1
DilDrainCfg.DailySched[2].
Start_h
Drain to dilute - Daily scheduler (Tuesday) -
hours
23
0
23
[h]
RW
HoldingRegister 133
1
DilDrainCfg.DailySched[2].
Start_min
Drain to dilute - Daily scheduler (Tuesday) -
minutes
0
0
59
[min]
RW
HoldingRegister 134
1
DilDrainCfg.DailySched[3].
Start_h
Drain to dilute - Daily scheduler (Wednesday)
- hours
23
0
23
[h]
RW
HoldingRegister 135
1
DilDrainCfg.DailySched[3].
Start_min
Drain to dilute - Daily scheduler (Wednesday) -
minutes
0
0
59
[min]
RW
HoldingRegister 136
1
DilDrainCfg.DailySched[4].
Start_h
Drain to dilute - Daily scheduler (Thursday) -
hours
23
0
23
[h]
RW
HoldingRegister 137
1
DilDrainCfg.DailySched[4].
Start_min
Drain to dilute - Daily scheduler (Thursday) -
minutes
0
0
59
[min]
RW
HoldingRegister 138
1
DilDrainCfg.DailySched[5].
Start_h
Drain to dilute - Daily scheduler (Friday) - hours
23
0
23
[h]
RW
HoldingRegister 139
1
DilDrainCfg.DailySched[5].
Start_min
Drain to dilute - Daily scheduler (Friday) -
minutes
0
0
59
[min]
RW
HoldingRegister 140
1
DilDrainCfg.DailySched[6].
Start_h
Drain to dilute - Daily scheduler (Saturday) -
hours
23
0
23
[h]
RW
HoldingRegister 141
1
DilDrainCfg.DailySched[6].
Start_min
Drain to dilute - Daily scheduler (Saturday) -
minutes
0
0
59
[min]
RW
HoldingRegister 142
1
DilDrainCfg.DailySched[7].
Start_h
Drain to dilute - Daily scheduler (Sunday) - hours 23
0
23
[h]
RW
HoldingRegister 143
1
DilDrainCfg.DailySched[7].
Start_min
Drain to dilute - Daily scheduler (Sunday) -
minutes
0
0
59
[min]
RW
HoldingRegister 144
2
PeriodicDrainThrsh
Set number of production hours between two
periodic total drain cycles
10
1
999
[h]
RW
HoldingRegister 146
1
ExtFanDTOn
Set start blower delay from start of production
0
0
600
[s]
RW
HoldingRegister 147
1
ExtFanDTOff
Set stop blower delay from end of production
90
0
600
[s]
RW
HoldingRegister 148
1
EvapCycleNoThrsh_S
Secondary unit number of evaporation cycles
setting for drain to dilute if micro-fi lling mode
not active (0=AUTO)
0
0
MaxEvap-
CycleNo
RW
HoldingRegister 149
1
FillTScale_Secondary
Secondary unit additional fi lling time modifi -
cation setting after reaching green LED level if
micro-fi lling mode not active
100
20
100
[%]
RW
HoldingRegister 150
1
DilDrainTScale_Secondary
Secondary unit drain time modifi cation setting
100
5
190
[%]
RW
HoldingRegister 304
2
ManMode_Fan1_PWM
Fan 1 speed setting in manual mode
Fan_1_cfg.
MinSpeed
Fan_1_
cfg.Max-
Speed
[rpm]
RW
HoldingRegister 306
2
ManMode_Fan2_PWM
Fan 2 speed setting in manual mode
Fan_2_cfg.
MinSpeed
Fan_2_
cfg.Max-
Speed
[rpm]
RW
HoldingRegister 308
2
ManMode_Fan3_PWM
Fan 3 speed setting in manual mode
Fan_1_cfg.
MinSpeed
Fan_1_
cfg.Max-
Speed
[rpm]
RW
HoldingRegister 310
2
Man_ProdReqM8
Manual production request
RW
HoldingRegister 312
1
MaxUnitProd
Set maximum production value
100.0
Regula-
tionCfg.
MinReq
100.0
0.1[%]
RW
InputRegister
1
1
SV_SWVer
Software version
RW
InputRegister
2
1
SV_OSVer
Operating system version
RW
InputRegister
3
1
UnitModel
Unit model
RW
InputRegister
4
2
MainPrb
Main probe reading
RW
InputRegister
6
2
LimitPrb
Limit probe reading
RW
InputRegister
8
2
PreheatPrb
Preheating probe reading
0.1[°C]/[°F] RW
InputRegister
10
1
Conductivity_Calc
Inlet water conductivity reading
20
1509
[uS/cm]
RW
InputRegister
11
1
WirelessPrbVal_1.Hum
Wireless probe 1 - Humidity value in %rH (SA and
SI probes only)
RW
InputRegister
13
1
WirelessPrbVal_1.Temp
Wireless probe 1 - Temperature value in °C
RW
InputRegister
15
1
WirelessPrbInfo_1.BattLev
Wireless probe 1 - Battery level from 0 to 3600
mV (below 2800 mV the battery level is low)
RW
InputRegister
16
1
WirelessPrbInfo_1.RadioSig-
nalLev
Wireless probe 1 - Radio signal level in dBm+100
(8-15 = LOW; 15-30 = MEDIUM, >30 = EXCEL-
LENT)
RW
InputRegister
17
1
WirelessPrbVal_2.Hum
Wireless probe 2 - Humidity value in %rH (SA and
SI probes only)
RW
InputRegister
19
1
WirelessPrbVal_2.Temp
Wireless probe 2 - Temperature value in °C
RW
InputRegister
21
1
WirelessPrbInfo_2.BattLev
Wireless probe 2 - Battery level from 0 to 3600
mV (below 2800 mV the battery level is low)
RW
InputRegister
22
1
WirelessPrbInfo_2.RadioSig-
nalLev
Wireless probe 2 - Radio signal level in dBm+100
(8-15 = LOW; 15-30 = MEDIUM, >30 = EXCEL-
LENT)
RW
InputRegister
23
1
WirelessPrbVal_3.Hum
Wireless probe 3 - Humidity value in %rH (SA and
SI probes only)
RW
InputRegister
25
1
WirelessPrbVal_3.Temp
Wireless probe 3 - Temperature value in °C
RW
InputRegister
27
1
WirelessPrbInfo_3.BattLev
Wireless probe 3 - Battery level from 0 to 3600
mV (below 2800 mV the battery level is low)
RW
InputRegister
28
1
WirelessPrbInfo_3.RadioSig-
nalLev
Wireless probe 3 - Radio signal level in dBm+100
(8-15 = LOW; 15-30 = MEDIUM, >30 = EXCEL-
LENT)
RW
InputRegister
29
1
WirelessPrbVal_4.Hum
Wireless probe 4 - Humidity value in %rH (SA and
SI probes only)
RW
InputRegister
31
1
WirelessPrbVal_4.Temp
Wireless probe 4 - Temperature value in °C
RW
InputRegister
33
1
WirelessPrbInfo_4.BattLev
Wireless probe 4 - Battery level from 0 to 3600
mV (below 2800 mV the battery level is low)
RW