User menu and unit confi guration
g0300122EN rel. 1.0 - 01.12.2021
12.9.7 Export parameters to U
SB
pen drive
The unit’s parameter confi gurations can be exported to USB pen drive, and subsequently loaded onto a second unit, making
installation and setup even faster. To save the parameters, plug the USB pen drive into the c.pHC and then go to screen Eg08 and
set the “Export?” parameter to “YES”.
Index
Parameter
Description
Eg08
Export parameters
Start exporting confi guration from unit to USB pen drive
Default: No
Tab. 12.ba
The exported fi le will automatically be saved in the pen drive’s root directory and will be called: “UG4cgg.txt”
12.9.8 Import parameters onto the unit
The unit’s parameter confi gurations can be imported from a USB pen drive. To import the parameters, make sure that the export-
ed fi le is in the pen drive’s root directory and is called: “UG4cgg.txt”. Then plug the USB pen drive into the c.pHC and go to screen
Eg09, and set the “Import?” parameter to “YES”.
Index
Parameter
Description
Eg09
Import parameters
Start importing confi guration from USB pen drive to unit
Default: No
Tab. 12.bb
12.10 Menu E.
S
ettings - h.
S
upervisor
12.10.1
S
upervisor network address setting (Installer menu)
Supervision can be enabled on the Ethernet network or BMS serial port. The following protocols are available to be set by the
user:
Port
Protocol
BMS
Carel, ModBus, BACnet
Ethernet
ModBus, BACnet
On screen Eh01, the port and supervisor protocol can be set, as well as the unit’s supervision address for the BMS port.
Index
Parameter
Description
Eh01
Unit supervision address
on BMS port
Set the unit’s supervision address and protocol for BMS port.
Default:
Address: 1; Protocol: Modbus; On/Off from SV: No;
Control from SV: No;
Possible settings:
Address: 1 to 247
Protocol type: Modbus, BACnet, Carel
Tab. 12.bc
Address is the device’s supervision address on the BMS port. Enabling or disabling the parameters “On/Off from SV” and “Control
from SV” activates or deactivates the response to the corresponding signals from the supervisor. For other supervisor protocols,
select Carel protocol and use the Carel external gateway (supernode for humidifi cation).
12.10.2
B
M
S
port (Installer menu)
Screen Eh02 is used to set supervisor communication on the BMS port.
Index
Parameter
Description
Eh02
BMS port
communication
settings
Set the supervisor communication parameters via BMS:
baud rate, stop bits and parity bits
Default:
Baud rate: 19200 Stop bits: 2
Parity: None
Tab. 12.bd
12.10.3
BAC
net M
S
/T
P
supervisor settings (Installer menu)
To set the address, maximum number of Main units and maximum number of frames for BACnet MS/TP supervision systems, use
screen Eh03. The screen is only displayed when supervision is confi gured on the BMS port with the BACnet protocol.
Index
Parameter
Description
Eh03
BACnet MS/TP
confi guration
Set the address, maximum number of Main units and maximum number of frames
Default: Address: 0
Max Mains: 127
Max frames: 10
Tab. 12.be