62
ENG
Checks before commissioning
g0300122EN rel. 1.0 - 01.12.2021
11.7
C
omplete programming tree
Below is the complete tree of the settings menu. The screen index at the top right (Fig. 11.s) corresponds to the sequence in each
menu in order to reach the specifi c page. There are two levels of access: Installer and Service.
To login to the settings menu, use the follow-
ing passwords:
• service
0044;
• installer:
0077.
Regulation
Ea01
Regulation type:
Mod. Hum. with limit
Fig. 11.s
Menu A. Clock
Index
Description
Level
A01
Set the time, date and time zone
Installer - Service
Menu B. Time bands (scheduler)
Index
Description
Level
B01
Enable time bands
Installer - Service
B02
(visible if time bands are enabled)
Set the time bands: day, on time, off time
Installer - Service
B03
Set the special periods
Installer - Service
B04
Set the special days
Installer - Service
Menu C. Alarm thresholds
Index
Description
Level
C01
Set alarm thresholds
Low humidity/temperature alarm threshold
High humidity/temperature alarm threshold Limit humidity/temperature alarm threshold
Installer - Service
Menu D. Inputs/outputs
Menu
Index
Description
Level
Analogue inputs
D01
Read values of main probe, limit probe, boiler water temperature, feedwater
conductivity
Installer - Service
Digital inputs
D02
Read status of remote On/Off , level sensor fl oat position, foam sensor
Installer - Service
Analogue outputs
D03
Read current production
Installer - Service
Digital outputs
D04
Read status of unit On/Off , drain pump, fi ll valve
Installer - Service
In/Out - WPrb 1
(In/Out Wireless Probe 1)
D05
Read temperature and/or humidity values
Read signal level and battery level on probe 1
Installer, Service
In/Out - WPrb 2
(In/Out Wireless Probe 2)
D06
Read temperature and/or humidity values
Read signal level and battery level on probe 2
Installer, Service
In/Out - WPrb 3
(In/Out Wireless Probe 3)
D07
Read temperature and/or humidity values
Read signal level and battery level on probe 3
Installer, Service
In/Out - WPrb 4
(In/Out Wireless Probe 4)
D08
Read temperature and/or humidity values
Read signal level and battery level on probe 4
Installer, Service
Burner 1
D09
Read fl ue gas values, fan speed, fl ame presence, Klixon status and gas
command
Installer, Service
Burner 2 (if present)
D10
Read fl ue gas values, fan speed, fl ame presence, Klixon status and gas
command
Installer, Service
Burner 3 (if present)
D11
Read fl ue gas values, fan speed, fl ame presence, Klixon status and gas
command
Installer, Service
Analogue inputs on sec-
ondary unit (if present)
D12
Read boiler water temperature, feedwater conductivity
Installer, Service
Digital inputs on
secondary unit (if present)
D13
Read status of remote On/Off , level sensor fl oat position, foam sensor
Installer, Service
Digital outputs on
secondary unit (if present)
D14
Read status of unit On/Off , drain pump, fi ll valve
Installer, Service
Tab. 11.g