Electrical connections
g0300122EN rel. 1.0 - 01.12.2021
CONTROL WITH ONE HUMIDITY PROBE
• short-circuit terminals 7U and 8U (jumper) to enable production; alternatively connect terminals 7U – 8U to a remote contact
(e.g.: switch, timer,...);
• connect the main active room probe to terminals 1U, 2U (GND) and 3U (+12Vdc);
• to enable control, set:
Notice:
when using 0-10 V probes, connect the probe power (G) to terminal “14” on the terminal block “T” inside
the electrical panel, rather than terminal 3U.
1U 2U 3U
4U 5U 6U
7U 8U
9U 10U 11U 12U 13U 14U
U
OU
T H/T
M
ain pr
obe
M
+ (G)
Fig. 9.m
Index Parameter
Description
Ea01
Control type
one humidity probe
Ea05
Modulating
control
Set: humidity set point (0-100 %rH)
diff erential (2-20 %rh)
Minimum production (25%-100%) -
Maximum production (25%-100%)
Ec01
Type of main
probe
Select from: 0 - 1V, 0 - 10V, 2 - 10V,
0 - 20mA, 4 - 20mA
Tab. 9.i
CONTROL WITH ONE HUMIDITY PROBE AND LIMIT PROBE
• short-circuit terminals 7U and 8U (jumper) to enable production; alternatively connect terminals 7U – 8U to a remote contact
(e.g.: switch, timer,...);
• connect the main active room probe to terminals 1U, 2U (GND) and 3U (+12Vdc);
• connect the active limit probe to terminals 5U, 3U (+12Vdc), 6U (GND);
• to enable control, set:
Index
Parameter
Description
Ea01
Control type
Humidity with limit probe
Ea05
Modulating control
Set: Humidity set point (0-100 %rH) Diff erential (2-20 %rh)
Minimum production (25%-100%) - Maximum production (25%-100%)
Ea06
Limit probe
Humidity set point (0-100 %rH) - Diff erential (20 %rh)
Ec01
Type of main probe
Select from: 0 - 1V, 0 - 10V, 2 - 10V, 0 - 20mA, 4 - 20mA
Ec02
Limit probe type
Select from: 0 - 1V, 0 - 10V, 2 - 10V, 0 - 20mA, 4 - 20mA
Tab. 9.j
Notice:
when using 0-10 V probes, connect the probe power (G) to terminal “14” on the terminal block “T” inside
the electrical panel, rather than terminal 3U.
1U 2U 3U
4U
5U 6U 7U 8U
9U 10U 11U 12U 13U 14U
U
OU
T H/T
M
ain pr
obe
M
+ (G)
OU
T H/T
S
e
cond pr
obe
M
+ (G)
The following probes can be connected:
probes for rooms
DPWC111000
for air ducts
DPDC110000,
DPDC210000
for industrial applications
DPPC210000
Tab. 9.k
Notice:
third-party active probes can also be
connected to the controller.
Fig. 9.n
CONTROL WITH TWO HUMIDITY PROBES
• short-circuit terminals 7U and 8U (jumper) to enable production; alternatively connect terminals 7U – 8U to a remote contact
(e.g.: switch, timer,...);
• connect the main active room probe to terminals 1U, 2U (GND) and 3U (+12Vdc);
• connect the second active probe to terminals 5U, 3U (+12Vdc) and 6U (GND);
• to enable control, set:
Index
Parameter
Description
Ea01
Control type
Modulation with two humidity probes
Ea02
Control with two probes
Set the weight of the two probes (0-100%)
Ea05
Modulating control
Set: humidity set point (0-100 %rH) diff erential (2-20 %rh)
Minimum production (25%-100%) - Maximum production (25%-100%)
Ec01
Type of main probe
Select from: 0 - 1V, 0 - 10V, 2 - 10V, 0 - 20mA, 4 - 20mA
Ec02
Second probe type
Select from: 0 - 1V, 0 - 10V, 2 - 10V, 0 - 20mA, 4 - 20mA
Tab. 9.l
The controller will calculate the weighted average between the two probes. The weight of the two probes can also be set.