Electrical connections
g0300122EN rel. 1.0 - 01.12.2021
power supply
rated characteristics
mod.
temperature
°C (°F)
voltage V
(1)
current A
power W
(2)
produc-
tion kg/h
(lbs/h)
(3)
no. of
heaters
cable size mm
2
AWG
(2)
line fuses
A - type
(2)
UG
line
heater line
UG
line
heater
line
UG line
heater line
UG line
line
heaters
UG045H1105
0 to 45
(32 to 113)
115V 1PH~
60 Hz
1.64 -
187 -
45 (100) -
2.5 - AWG 14
10 - F
UG045X1105
-40 to 45
(-40 to 113)
115V 1PH~
60 Hz
2.16 17.39
248 2000
45 (100) 2
2.5 - AWG 14
6 - AWG 10
10 - F
25 - F
UG090H1105
0 to 45
(32 to 113)
115V 1PH~
60 Hz
2.22 -
255 -
90 (200) -
2.5 - AWG 14
10 - F
UG090X1105
-40 to 45
(-40 to 113)
115V 1PH~
60 Hz
2.71 17.39
312 2000
90 (200) 2
2.5 - AWG 14
10 - F
25 - F
UG150H1105
0 to 45
(32 to 113)
115V 1PH~
60 Hz
2.68 -
309 -
150
(330)
-
2.5 - AWG 14
10 - F
UG150X1105
-40 to 45
(-40 to 113)
115V 1PH~
60 Hz
3.20 17.39
368 2000
150
(330)
2
2.5 - AWG 14
6 - AWG 10
10 - F
25 - F
UG180H1105
0 to 45
(32 to 113)
115V 1PH~
60 Hz
3.38 -
389 -
180
(400)
-
2.5 - AWG 14
10 - F
UG180X1105
-40 to 45
(-40 to 113)
115V 1PH~
60 Hz
4.42 17.39
509 2000
180
(400)
2
2.5 - AWG 14
6 - AWG 10
10 - F
25 - F
UG300H1105
0 to 45
(32 to 113)
115V 1PH~
60 Hz
4.34 -
500 -
300
(660)
-
2.5 - AWG 14
10 - F
UG300X1105
-40 to 45
(-40 to 113)
115V 1PH~
60 Hz
5.38 17.39
619 2000
300
(660)
2
2.5 - AWG 14
6 - AWG 10
10 - F
25 - F
UG450X1105
-40 to 45
(-40 to 113)
115V 1PH~
60 Hz
8.06 34.78
927 4000
450
(990)
4
2.5 - AWG 14
16 - AWG 4
10 - F
50 - F
Tab. 9.b
(1)
Tolerance allowed on the nominal mains voltage: -15% +10%
Tolerance allowed on the nominal mains frequency: ± 1 %.
(2)
Recommended values; referred to cables laid in closed PVC or rubber conduits 20 m long.
(3)
Instant steam production: average steam production may be aff ected by external factors, such as: ambient temperature,
water quality, steam distribution system.
Notice:
the power cable must be sized in compliance with the local regulations in force. The humidifi er power supply line
must be equipped with an disconnect switch and protection fuses suitably sized for the short-circuit current, to be fi tted by the
installer.
Notice:
on the outdoor models, the heaters, where featured, must have its own independent power supply line, not
shared with the humidifi er.
9.1.4
A
uxiliary circuit transformer
The multi-voltage auxiliary circuit transformer has a primary winding for 230 V (protected by fuses, 10.3x38 mm) and a secondary
winding (24 V). The transformer is connected and checked in the factory, according to the rated voltage.
9.1.5 Main control board
The auxiliary connections must be made by inserting the cables into the electrical panel compartment through the cable glands
on the side (1 - Fig. 9.i) or on the bottom of the humidifi er (2 - Fig. 9.a, UL outdoor versions only). It is recommended to secure the
probe, remote ON/OFF contact connection cables etc. with appropriate cable ties, in order to prevent disconnection.
1T 2T 3T 4T 5T 6T 7T 8T 9T 10T 11T 12T 13T 14T
1Z 2Z 3Z 4Z 5Z 6Z 7Z 8Z 9Z 10Z 11Z 12Z
1S 2S 3S 4S 5S 6S 7S 8S 9S 10S 11S 12S 13S 14S
T
1Y 2Y 3Y 4Y 5Y 6Y 7Y 8Y 9Y
Y
1O 2O 3O 4O 5O 6O 7O 8O 9O
O
S
* Z
L1 L2 GND
AL
1U 2U 3U 4U 5U 6U 7U 8U 9U 10U 11U 12U 13U 14U
U
1A 2A 3A 4A
A
Notice:
terminal block Z is only available on UG180.
Fig. 9.d