89
ENG
Supervisor network
g0300122EN rel. 1.0 - 01.12.2021
15. SUPERVISOR NETWORK
15.1 Table of supervisor variables
The variables shown in the list are a set of all the internal variables on the gaSteam humidifi er.
DO NOT CONFIGURE ANY VARIABLES THAT ARE NOT SHOWN IN THE TABLES, OTHERWISE HUMIDIFIER OPERATION MAY BE
AFFECTED.
15.1.1 Table of
C
arel variables
The variables used for the Carel protocol are shown below.
RW= Read/Write
Type
Add. Variable name
Description
Def.
Min
Max
UoM
Access
Analogue 1
ManReq
Set production request in manual mode
Percent
RW
Analogue 2
GlbSetP_Hum
Set humidity value (humidity set point)
50.0
0
100.0
PercentRelative
Humidity
RW
Analogue 3
GlbSetP_Temp
Set temperature value (temperature set point)
42.0
0
100.0
DegreesCelsius
RW
Analogue 4
RegulationCfg.Hyst
Unit control parameters - Control hysteresis
2.0
0.5
100.0
RW
Analogue 5
RegulationCfg.Diff
Unit control parameters - Diff erential (for modulating
control)
5.0
RW
Analogue 6
GlbSetPLim_Hum
Set humidity limit value (humidity limit set point)
100.0
0
100.0
PercentRelative
Humidity
RW
Analogue 7
GlbSetPLim_Temp
Set temperature limit value (temperature limit set point)
50.0
0
100
DegreesCelsius
RW
Analogue 8
RegulationCfg.Diff Lim
Unit control parameters -
Limit diff erential (for modulating control)
5.0
RW
Analogue 9
RegulationCfg.MinReq
Unit control parameters -
Minimum request
4.0
25.0
MaxUnit-
Prod
Percent
RW
Analogue 10
AlrmThrshHumLo
Set main probe low humidity alarm threshold
0.0
AlrmThrsh-
HumHi
PercentRelative
Humidity
RW
Analogue 11
AlrmThrshHumHi
Set main probe high humidity alarm threshold
100.0
AlrmThrsh-
HumLo
PercentRelative
Humidity
RW
Analogue 12
AlrmThrshHumHiLim
Set limit probe low humidity alarm threshold
100.0
0
100.0
PercentRelative
Humidity
RW
Analogue 13
AlrmThrshTempLo
Set main probe low temperature alarm threshold
0.0
AlrmThr-
shTempHi
DegreesCelsius
RW
Analogue 14
AlrmThrshTempHi
Set main probe high temperature alarm threshold
60.0
AlrmThr-
shTempLo
DegreesCelsius
RW
Analogue 15
AlrmThrshTempHiLim
Set limit probe low temperature alarm threshold
60.0
DegreesCelsius
RW
Analogue 16
MainPrbCfg.Mi_Hum
Main probe confi guration -
Minimum for humidity control
0
0
100
PercentRelative-
Humidity
RW
Analogue 17
MainPrbCfg.Ma_Hum
Main probe confi guration -
Maximum for humidity control
100.0
0
100
PercentRelative-
Humidity
RW
Analogue 18
MainPrbCfg.Mi_Temp
Main probe confi guration -
Minimum for temperature control
-20.0
DegreesCelsius
RW
Analogue 19
MainPrbCfg.Ma_Temp
Main probe confi guration -
Maximum for temperature control
70.0
DegreesCelsius
RW
Analogue 20
LimitPrbCfg.Mi_Hum
Limit probe confi guration -
Minimum for humidity control
0
0
100
PercentRelative-
Humidity
RW
Analogue 21
LimitPrbCfg.Ma_Hum
Limit probe confi guration -
Maximum for humidity control
100.0
0
100
PercentRelative-
Humidity
RW
Analogue 22
LimitPrbCfg.Mi_Temp
Limit probe confi guration - Minimum for humidity control
-20.0
DegreesCelsius
RW
Analogue 23
LimitPrbCfg.Ma_Temp
Limit probe confi guration -
Maximum for temperature control
70.0
DegreesCelsius
RW
Analogue 24
RegulationCfg.PwrCor-
rectionFactor
Unit control parameters -
Correction factor (0=no correction)
29.0
RW
Analogue 25
SchedDayCfg[0].SetP
Scheduler - Set point for ON+SET mode (2) (Monday)
RW
Analogue 26
SchedDayCfg[1].SetP
Scheduler - Set point for ON+SET mode (2) (Tuesday)
RW
Analogue 27
SchedDayCfg[2].SetP
Scheduler - Set point for ON+SET mode (2) (Wednesday)
RW
Analogue 28
SchedDayCfg[3].SetP
Scheduler - Set point for ON+SET mode (2) (2) (Thursday)
RW
Analogue 29
SchedDayCfg[4].SetP
Scheduler - Set point for ON+SET mode (2) (2) (Friday)
RW
Analogue 30
SchedDayCfg[5].SetP
Scheduler - Set point for ON+SET mode (2) (Saturday)
RW
Analogue 31
Man_ProdReqM8
Manual production request
RW
Analogue 32
MainPrb
Main probe reading
RW
Analogue 33
LimitPrb
Limit probe reading
RW
Analogue 34
PreheatPrb
Preheating probe reading
DegreesCelsius
RW
Analogue 35
CurrProdPh
Current production
0
NomProd
KilogramsPerHour RW
Analogue 36
NetReq
Total current production as a % (M/S mode only)
Percent
RW
Analogue 37
NetProd
Total current production in kg/h / lb/h (M/S mode only)
Kilograms
RW
Analogue 38
Burner_1_Tach
Fan 1 speed reading
Revolutions
PerMinute
RW
Analogue 39
Burner_2_Tach
Fan 2 speed reading
Revolutions
PerMinute
RW
Analogue 40
Burner_MB_3_Tach
Fan 3 speed reading
Revolutions
PerMinute
RW
Analogue 41
Temp_Fumes_1
Flue gas temperature - Probe 1 reading
DegreesCelsius
RW
Analogue 42
Temp_Fumes_2
Flue gas temperature - Probe 2 reading
DegreesCelsius
RW
Analogue 43
Temp_Fumes_MB_3
Flue gas temperature - Probe 3 reading
DegreesCelsius
RW
Analogue 44
Fan1_PWM
Fan 1 speed set point
0.0
1000.0
RW
Analogue 45
Fan2_PWM
Fan 2 speed set point
0.0
1000.0
RW
Analogue 46
Fan3_PWM
Fan 3 speed set point
0
100.0
RW
Analogue 47
Fan1_SetSpeed
Fan 1 speed setting
RW
Analogue 48
Fan2_SetSpeed
Fan 2 speed setting
RW
Analogue 49
FoamLevReal
Signal reading from foam sensor
RW
Analogue 56
RegulationCfg.W_MinT-
empThrsh
Set water preheating temperature
70.0
50.0
80.0
DegreesCelsius
RW
Analogue 57
PreheatOff set_Temp
Set temperature diff erence with reference to temperature
set point for activation of preheating (preheating off set)
3.0
2
20.0
DegreesCelsius
RW