Checks before commissioning
g0300122EN rel. 1.0 - 01.12.2021
11.6.5
S
et point setting
The Setpoint tab is used to set the set point (1 - Fig. 11.q), the proportional band (2 - Fig. 11.q) and the maximum production
(3 - Fig. 11.q).
300090
_11
2
_
R02
1
2
3
Fig. 11.q
11.6.6
S
ystem information
The System information tab shows information on the status and activity of the humidifi er, as well as on the software and hard-
ware.
300090
_111_
R02
1
Fig. 11.r
The unit status is shown on the display, as indicated in the fi gure (1 - Fig. 11.r):
Unit status
Description
Standby
unit in standby and ready to operate
Production
the unit is producing steam
Alarm
there is at least one active alarm. Display the alarm by pressing the button
Off from BMS
steam production disabled by the supervisor
Off from scheduler
steam production disabled due to set time band
Off from DIN
production of steam stopped due to opening of the “remote ON/OFF” contact;
Off from keypad
the unit has been switched off from the keypad
Off from monitoring
steam production disabled by the monitoring service
Ready for backup
the unit is ready and awaiting to start operation if there is a fault on the main unit.
Manual mode
test mode for commissioning and to check functions (for example: activate drain pump, activate fi ll valve...)
Warning
warning notifi cation
Preheating
the unit is preheating the water in the boiler
Preheat at start
at start-up, the unit heats the water to reach the production request
Autotest
the unit is running the autotest
Drain due to inactivity water drain due to inactivity or periodically, the drain pump is operating
Tab. 11.f
11.6.7
D
escriptive icon of humidifi er status
Graphic display of unit status via animated icons. The status may be:
• Fill (fi ll valve active);
• Drain (drain pump active);
• Steam
production;
• Minimum water level in the boiler (yellow and red LEDs on);
• Water level above the maximum in the boiler (green LED on);