Installation notes
g0300122EN rel. 1.0 - 01.12.2021
gaSteam/access point connection:
To connect the humidifi er to the access point, use the Fieldbus connection on terminal M3 (M3.1: Tx/Rx-, M3.2: Tx/Rx+, M3.3:
GND):
Fig. 6.r
Notice:
the devices have a range of
around a hundred metres in a free space, i.e.
without any obstacles. In a closed space, the
range varies considerably depending on the
type of environment and the surrounding
objects (shelves, metal partition walls etc.).
If installing multiple wireless probes, the controller will calculate the weighted average between the various probe readings,
depending on the settings made by the user and the defi ned probe groups. Also see the paragraph “Wireless probes”. The con-
troller also displays (locally only) the battery and signal level for each probe (screens D05 to D08). The table below shows the part
numbers and descriptions of the devices that can be used:
Code
Model
Specifi cations
Power supply
WS01F01M00
SI sensor
Temperature/humidity
for industrial use
Battery
WS01G01M00
SA sensor
Room temperature/humidity
Battery
WS01AB2M20
Access Point
ZigBee™
– RS485 Modbus® wireless gateway
12-24 Vac/dc ±10% 100 mA; 50/60 Hz;
Use a Class II safety transformer
with a minimum power rating of 2 VA.
A 12 Vac transformer is recommended
Tab. 6.g
6.11
W
ireless probe installation
The main steps for installing the wireless devices are:
• power up the access point (12/24 Vac/dc ±10%m, 100 mA) and complete the initialisation procedure, creating the network
and selecting the channel;
• after having opened the domain on the access point, complete the binding procedure so as to uniquely identify each probe.
The address to be used by the access point is set using the dipswitches on the device, and is the following:
DIP:
1 2 3 4
+
+ G
-
-
Rx- Rx+ GND
L1L2 L3
T1
DIP 1-2-3 selezione indirizzo di rete
DIP 4 selezione baud di rete
Dipswitch
Access Point
Access Point
Serial port baud rate (bit/s)
N82
1
2
3
4
2
19200
OFF ON
OFF ON
Tab. 6.h
Fig. 6.s
This assigns the address 2 to the access point, with a baud rate (bit/sec) of 19200 (N82). The addresses of the four serial probes,
on the other hand, must be set as shown in the table below:
Address
Dipswitch
1
2
3
4
5
6
7
8
Probe 1
16
0
0
0
0
1
0
0
0
Probe 2
17
1
0
0
0
1
0
0
0
Probe 3
18
0
1
0
0
1
0
0
0
Probe 4
19
1
1
0
0
1
0
0
0
Tab. 6.i
Remember to verify the quality of the wireless signal between the access
point and each wireless probe. For a complete description of the installa-
tion procedure, see the manual on the corresponding probes and access
point. To confi gure the probes, see screens: Ec03, Ec04, Ec05, Ec06 and
Ec07 described under “Wireless probes”. In particular, screen Ec03 is used
to enable the wireless probes connected to the access point, knowing that
addresses 16, 17, 18 and 19 are Probe 1, Probe 2, Probe 3 and Probe 4 re-
spectively.
Configuration
Ec03
Wireless probes
Probe 1:
Probe 2:
Probe 3:
Probe 4:
Main probe
Not used
Not used
Not used
Fig. 6.t
network address selection
baud rate selection