Steam distribution
g0300122EN rel. 1.0 - 01.12.2021
8.1.3 Linear distributor models and typical installations
gaSteam
humidifi er outlet Ø mm
80
(3.1”)
80
(3.1”)
2 x 80
(2 X 3.1”)
2 x 80
(2x 3.1”)
3 x 80
(3x 3.1”)
humidifi er capacity kg/h
45
90
150
180
300
450
distributor inlet (ØA)
mm (in)
max distributor
capacity kg/h (lbs/h)
minimum width
of duct/AHU mm
(in)
part number
UG045 UG090 UG150 UG180
UG300
UG450
40 (1.6”)
25 (55)
850 (33.5”)
DP085D40RH
2
(4)**
See Fig. 8.h
40 (1.6”)
35 (77)
1050 (41.3”)
DP105D40RH
2
(4)**
40 (1.6”)
45 (99)
1250 (49.2”)
DP125D40RH
2
2
4
4
40 (1.6”)
45 (99)
1650 (65”)
DP165D40RH
2
2
4
4
40 (1.6”)
45 (99)
2050 (80.7”)
DP205D40RH
2
4
4
40 (1.6”)
25 (55)
850 (33.5”)
DP085D40R0
2
(4)**
40 (1.6”)
35 (77)
1050 (41.3”)
DP105D40R0
2
(4)**
40 (1.6”)
45 (99)
1250 (49.2”)
DP125D40R0
2
2
4
4
40 (1.6”)
45 (99)
1650 (65”)
DP165D40R0
2
2
4
4
40 (1.6”)
45 (99)
2050 (80.7”)
DP205D40R0
2
4
4
40 (1.6”)
45 (99)
600 (23.6”)
DP060D40RU
2
2
4
4
Tab. 8.f
if the duct does not feature the required width for the distributor, two shorter distributors (numbers indicated in brackets) can
be used, branching the steam hose.
*: use “Y” kit UEKY000000, 40 mm (1.6”) inlet and 2 x 30 mm (1.2”) outlets
**: use “Y” kit UEKY40X400, 40 mm (1.6”) inlet and 2 x 40 mm (1.6”) outlets
For the typical installations of linear distributors, see the fi gure below:
≥70 mm
min.
200 mm
1/3 H
H >250 mm
1/3 H
≥200 mm
H >250 mm
min 200 mm
=
=
1/7 H
2/7 H
2/7 H
H >600 mm
1/5 H
2/5 H
≥200 mm
H >350 mm
1/5 H
2/5 H
H > 400 mm
1/7 H
2/7 H
2/7 H
H > 500 mm
H > 200 mm
=
=
1/2 H
H >300 mm
=
=
=
=
H >500 mm
=
1/3 H
1/3 H
=
1
2
3
4
5
6
7
8
10
11
9
Fig. 8.e
Note: