Room Layout
OMNERA™400T
0180-095-485
Planning Guide
Page 5-19
The length of the cables between the outlet and the system cabinet, restricts where the system
cabinet can be placed.
No.
From
To
Cable channel
cross section
(min)
Conduit, diame-
ter (min)
Length from outlet
(max)
1
CS
SC
1320mm
2
60mm
6m (16m) and 13m
(24m)
2
Table SC
525mm
2
70mm
15m
3
WS
SC
420mm
2
70mm
15m
4
SC
C. Room
81mm
2
45mm
21m