7.3.5
Wiring the 110...240 V AC electrical supply for a
8619 multiCELL WM AC
Protective cover
PE
PE
PE
M0
M1
M2
M3
M4
M5
M6
PWR OUT
MEMORY
CARD
→
Unscrew and remove the
protective cover of the power
supply connection terminal
block.
110-240 V~
50/60 Hz
PE
L
N
PE
L
N
PE
110-240 V~
50/60 Hz
L N
Removable screw
terminals, 2-positions,
green
→
Use the rightmost cable
gland for the electrical power
supply cable.
→
Wire the 110...240 V AC
power supply for a
8619 multiCELL WM AC
on a terminal block marked
110...240 V AC.
→
Connect the protective earth
of the installation to the earth
screw of the device (see
section 5, Fig. 3) using a
lug with an eyelet, suitable
for the M4 earth screw and
earth conductor. Tighten with
a torque of 1 N·m ±20%
(0,74 lbf·ft ±20%).
L: Live conductor
N: Neutral conductor
→
Put in place and screw on the
protective cover.
Fig. 15 : Wiring the 110...240 V AC electrical supply for a 8619 multiCELL WM AC