8.11.4 Calibrating an analogue input AI1 or AI2 connected to a
sensor other than a chlorine sensor
Refer to section 8.9 to access the "Calibration" menu.
Mx:Inputs
PV offset calibration
AI1/AI2
2-point PV calibration
1st point
2nd point?
2nd point
Calibr. result
YES
NO
Calibration
Voltage calibration
Current calibration
1st point
2nd point
Calibr. result
1st point
Calibr. result
Mode:general
Calibration intervals
Calibration
Last
Reset Cali-
bration Timer
ENTERING
Maintenance
Last
Reset Mainte-
nance Timer
ENTERING
Yes/No
Yes/No
Factory calibration
Yes/No
If "Mode" = "Voltage"; See section 8.10.21.
If "Mode" = "Current"; See section 8.10.21.
VALUE
VALUE
If a measuring sensor (other than a chlorine measuring sensor) is connected to an AI1 or AI2 analogue intput, the
analogue input can be calibrated:
• either with respect to the measured value, at two points or at one point. See section 8.11.6 Calibrating an
analogue input, AI1 or AI2, at two points, with respect to a measured value other than chlorine or section 8.11.7
Calibrating an analogue input, AI1 or AI2, at one point (offset), with respect to a measured value other than
chlorine.
• or with respect to the current or voltage received on the input. See section 8.11.8 Calibrating an analogue input
connected to a current output or a voltage output.
→
To read the date of the last calibration of an analogue input, see section 8.11.11.
→
To enter the periodicity of calibrations, see section 8.11.12.
→
To read the date of the last maintenance operation carried out on the sensor connected to the analogue input,
see section 8.11.13.
→
To enter the periodicity of a maintenance operation to be carried out on the sensor connected to the analogue
input, see section 8.11.14.
→
To return to the calibration parameters for the analogue input, as carried out in the factory, see
section 8.11.15.
134
Adjustmentandcommissioning
Type 8619
English
Summary of Contents for 8619 multiCELL WM AC
Page 6: ...6 English ...
Page 12: ...12 Type 8619 English ...
Page 24: ...24 Type 8619 English ...
Page 40: ...40 Type 8619 English ...
Page 70: ...70 Installation and wiring Type 8619 English ...
Page 180: ...180 Type 8619 English ...
Page 192: ...192 Type 8619 English ...
Page 193: ......
Page 194: ...www burkert com ...