7
INSTALLATION AND WIRING
7.1
Safety instructions
DANGER
Risk of injury due to electrical voltage.
▶
If a 12..36 V DC wall-mounted version is installed either in a wet environment or outdoors, all the electrical
voltages must be of max. 35 V DC.
▶
Before carrying out work on the system, disconnect the electrical power for all the conductors and isolate it.
▶
All equipment connected to the device must be double insulated with respect to the mains according to the
standard IEC 61010-1:2010.
▶
Observe all applicable accident protection and safety regulations for electrical equipment.
WARNING
Risk of injury due to non-conforming installation.
▶
Electrical installation can only be carried out by qualified and skilled staff with the appropriate tools.
▶
Fit a circuit breaker or a switch to the electrical installation in which the device is installed.
▶
Install the circuit breaker or the switch in a place which is easy to reach.
▶
Identify the circuit breaker or the switch as the electrical power cut-off system for the device.
▶
Install appropriate overload safety devices. For a version powered by 110...240 V AC, insert overcurrent pro-
tective devices in the live conductor and in the neutral conductor.
▶
Do not power a device, version 12...36 V DC, with an alternating voltage or with a direct voltage higher than
36 V DC.
▶
Do not power a device, version 110...240 V AC, with a direct voltage or with an alternating voltage higher
than 240 V AC.
▶
Observe the standard NF C 15-100 / IEC 60634.
▶
Use preferably probes or sensors sold by Bürkert.
▶
Read and follow the Operating Instructions manuals of all the instruments connected to the device.
▶
On a 8619 multiCELL WM, only authorized personnel may insert in or remove the memory card from the
reader/recorder.
Risk of injury due to unintentional switch on of power supply or uncontrolled restarting of the
installation.
▶
Take appropriate measures to avoid unintentional activation of the installation.
▶
Guarantee a set or controlled restarting of the process subsequent to any intervention on the device.
For the Ethernet installation, observe the standard ISO / IEC 61918.
Protect this device against electromagnetic interference, ultraviolet rays and, when installed outdoors, the
effects of the climatic conditions.
42
Installationandwiring
Type 8619
English
Summary of Contents for 8619 multiCELL WM AC
Page 6: ...6 English ...
Page 12: ...12 Type 8619 English ...
Page 24: ...24 Type 8619 English ...
Page 40: ...40 Type 8619 English ...
Page 70: ...70 Installation and wiring Type 8619 English ...
Page 180: ...180 Type 8619 English ...
Page 192: ...192 Type 8619 English ...
Page 193: ......
Page 194: ...www burkert com ...