8.10.20 Choosing the units for the totalisers
This function is available on the devices with analysis modules if the software option, "FLOW", is activated. See
section 8.10.4.
Refer to section 8.9 to access the "Parameters" menu.
This is
when the
device is be-
ing parame-
tered............
....................
Parameters
This is
when the
device is be-
ing parame-
tered............
....................
M0:Inputs
DI1/DI2
Totaliser unit A
Totaliser unit B
Mx:Inputs
The function makes it possible to select the units of the totalisers displayed in the process level or sent to the
PLC (if the device has an Ethernet module).
8.10.21 Setting the parameters of the analogue inputs
Refer to section 8.9 to access the "Parameters" menu.
AI1/AI2
Mode:
Current
None
Voltage
Range:
0...20 mA
Format:
0
20 mA:
ENTERING
Unit
List of untis
Manual entry
This is
when the
device is be-
ing parame-
tered............
....................
Mx:Inputs
0...2 V
0...5 V
0...10 V
4...20 mA
if "Mode" = "Current"
if "Mode" = "Voltage"
0.00
0.000
0.0
0 mA/4 mA:
ENTERING
Filter:
Fast
None
Slow
2 V / 5 V / 10 V:
ENTERING
0 V:
ENTERING
if "Mode" = "Current"
if "Mode" = "Voltage"
This is
when the
device is be-
ing parame-
tered............
....................
Parameters
MODE
: Choose the input signal type, current or voltage.
RANGE
: Choose the range of the input signal, depending on the choice made in "MODE".
FORMAT
: Choose the number of displayed decimals.
UNITS
: Choose the units of the process input associated to the input signal within a predefined list or enter it.
0/4 MA
: Enter the value of the previously selected physical parameter (AI1/AI2), which is associated to a 0/4 mA
input current. Instead of being entered, the value can be automatically determined using the function "PV cali-
bration" in the menu "Calibration -> Mx:Inputs -> AI1 or AI2". See section .8.11.8.
20 MA
: Enter the value of the previously selected physical parameter (AI1/AI2), which is associated to a 20 mA
input current. Instead of being entered, the value can be automatically determined using the function "PV cali-
bration" in the menu "Calibration -> Mx:Inputs -> AI1 or AI2". See section 8.11.8.
117
Adjustmentandcommissioning
Type 8619
English
Summary of Contents for 8619 multiCELL WM AC
Page 6: ...6 English ...
Page 12: ...12 Type 8619 English ...
Page 24: ...24 Type 8619 English ...
Page 40: ...40 Type 8619 English ...
Page 70: ...70 Installation and wiring Type 8619 English ...
Page 180: ...180 Type 8619 English ...
Page 192: ...192 Type 8619 English ...
Page 193: ......
Page 194: ...www burkert com ...