: configuration position for the power supply
function(√means that this function is available, X means
that this function is not available)
Typ
power supply
ManageMenT FuncTion
sMarT power FuncTion
0
×
×
1
√
√
2
×
√
Power supply management
:
In the systems with a standby battery (optional), in case of AC
power cut the handset will automatically enter energy saving
mode, saving energy for the alarm function . For systems with
alarm function and standby battery it is recommended that
the power supply management is kept on .
Smart power supply
:
This allows the max quantity of working small EP when
power is supplied normally . For projects including small EP,
we suggest that the power supply is used as auxiliary power
supply and that the smart power supply function is kept on .
When type=0, no configuration is necessary .
ASR
:
alarm sinking reserve of each apartment supplied by the PS
asr = alarM sinking reserve oF each aparTMenT supplied by The ps
0
300 mA (Default (Max))
1
0 mA
2
50 mA
3
85 mA
4
120 mA
5
150 mA
6
180 mA
7
210 mA
8
240 mA
9
270 mA
LE
:
configuration position for smart power supply function .
This position controls when to enter energy-saving mode
under different situations .
0 AC
is not an not energy saving
1 AC
is not an not energy saving
NOT energy saving:
all the system functions are allowed .
This mode is not Energy saving . Energy saving: parts of the
system functions (such as video) are disabled in order to
save energy .
Example (A):
This riser has 20 floors, and each floor has 4 handsets . This
power supply manages 1-2 floors . If necessary enable the
smart power function and power management function,
the power supply address is 12, the max current of the alarm
sensor is 300 mA . System configuration mode 1 is used . The
power supply configuration should be as follows:
posiTion Mode 1 value For conFiguraTor reMarks
CF1
N
0
CF2
N
1
CF3
N
2
CF4
FF Min
0
CF5
FF Min
1
CF6
#II
Default is 4 apartments.
0 means 4 apartments0.
CF7
#II
CF8
FF Max
0
CF9
FF Max
2
CF10
CF10
For mode 1 and mode 2, CF10
and CF11 do not apply
CF11
CF11
CF12
Type
1
CF13
ASR
0
CF14
M
0
CF15
LE
0
323005 - power supply conFiguration
Accessory configuration examples