106
VIDEO DOOR ENTRY SYSTEM -
CONFIGURATION
D45
With mode 1 and mode 2, if configurator or keyboard
configuration is selected for the riser shunt, the following
conditions must be met: all riser shunts in the system should be
numbered in sequence . They must start from 1 and no number
can be missed .
Riser shunt software version V .2 or above includes the EP
offset configuration item . This item should be downloaded
from 323020 (version on V0 .7 or later version have this
function) . This added configuration is to ensure compatibility
between D45 system and BT 2-wire system . If the projects
does not require that these two systems be compatible,
configuration of this item is not necessary .
EP range of each cell in the D45 system is 1—80 . The main
EP range is also 1—80, which means that the maximum
Note: Riser shunt software version V.2 or above includes the EP offset configuration item. And it can only configurate by 323020, meanwhile 323020 version should be on or
above V0.7.
323003 - riser shunt conFiguration
number of the main EP in the system is 80, and the main
quantity that can be reached is 80*X (X is the cell quantity) .
But after D45 and BT 2-wire system compatible, each riser EP
and main EP can’t separately occupy 1-80 number . The main
EP QTY and EP total quantity for all risers cannot exceed 80 .
This means that the total quantity of riser EP +main EP<=80 .
Example
If D45 should be compatible with the BT system, there
are two D45/IP interfaces used in system . First D45/IP
interface-1, to connect 2 main EP and 3 cells (Cell 1, 2, 3),
each cell has one EP; second D45/IP interface-2, to connect
0 main EP and 3 cells (cell 4, 5, 6), cell 4 and cell 6 connect to
1 EP each, cell 5 connects to 2 EP .
Accessory configuration examples
323011-1 Entrance panel setting
EP Device
Riser SCS BUS Address
EP shifting Address setting
in RS1
Backbone SCS BUS Address
Lowest address
Highest address
First WEP
1
——
1
1
5
Second WEP
2
——
2
EP of Unit 1
1
2
1+2=3
EP of Unit 2
1
3
1+3=4
EP of Unit 3
1
4
1+4=5
IT4-2 Entrance panel setting
EP Device
Riser SCS BUS Address
EP shifting Address setting
in RS1
Backbone SCS BUS Address
Lowest address
Highest address
EP of Unit 4
1
5
1+5=6
6
9
First EP of Unit 5
1
6
1+6=7
Second EP of Unit 5
2
2+6=8
EP of Unit 6
1
8
1+8=9
Pc
HUB
323011
Main EP
322010
323011
323003
323003
323003
323003
323003
323003
323004
Main EP
322010
Riser EP
322010
Riser EP
322010
Riser EP
322010
Riser EP
322010
Riser EP
322010
Riser EP
322010
Riser EP
322010
N°1
N°2
N°3
N°4
N°5
N°6
N°7
N°8
N°9
cF11 cF12 = o3
cF13 cF14 = 01
cF11 cF12 = o4
cF13 cF14 = 01
cF11 cF12 = o5cF13
cF13 cF14 = 01
cF11 cF12 = o6
cF13 cF14 = 01
cF11 cF12 = o7
cF13 cF14 = 02
cF11 cF12 = o8
cF13 cF14 = 01