September 2021
Installation, Operation and Maintenance Manual
VCIOM-01249-EN Rev. 0
92
View Routines
Section 11: Maintenance
Section 11: Maintenance
11.1
Standard Maintenance
Approx. every 2 years:
Under normal operating conditions, the F01-2000 is maintenance-free: no actuator
maintenance is formally required, even though visual inspection for oil leakage or external
visible damages is recommended every two years. When conditions are severe (frequent
operation or high temperatures), inspect the oil level and oil quality more often. Replace all
seals that permit oil leakage or water ingress.
NOTICE
Before starting any maintenance operation, make sure that the mains and all other service
voltage connected to terminal board are switched-off.
!
WARNING
The actuator is non-intrusive. The control compartment was sealed in dry and clean
conditions and contains no site serviceable components. Do not open it unless absolutely
necessary. Unauthorized access will invalidate the warranty.
!
WARNING
Since the control compartment contains a 3.6 V lithium battery, only open it in safe area.
If the actuator is located in a hazardous area a “hot work” permit must be obtained unless
the actuator can be moved to a non-hazardous area.