September 2021
Installation, Operation and Maintenance Manual
VCIOM-01249-EN Rev. 0
56
Set-Up Routines
Section 9: Set-Up Routines
9.1.4
Remote Controls
The actuator may be remotely controlled by 4, or 3, or 2 wires depending on
the connection made on the terminal board of the actuator. The following options
are available:
•
4 wires latched: requires 2 momentary signals (since the control is self-maintained)
to open or close and one signal to stop in mid-travel. The action of the stop
signal can be reversed (stop when signal is On [MAKE] or stop when signal is Off
[BREAK]).
•
3 wires latched instant reverse: requires 2 momentary signals (since the
control is self-maintained) to open or close. Reverse momentary signal reverses
the direction.
•
3 wires momentary: requires 2 push-to-run type signals (since the control is not
self-maintained) to open or close.
•
2 wires open if signal On: requires signal On to open and no signal to close.
•
2 wires open if signal Off: requires signal Off to open and signal On to close.
By selecting the option Off, the remote controls are disabled. Configuration should be
done during actuator set-up.
Configuration procedure
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and then enter the password according to the instructions
(see “Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press YES to select actuator set-up menu, press NO to scroll the list
of available routines and then press YES to select Remote controls.
•
Press YES if the control mode is correct or NO to scroll the list of available options:
4 wires, 3 wires, 2 wires, off. Press YES to select the desired option. If 4 wires was
chosen use YES and NO to select the STOP signal: set MAKE to stop when signal is
on and set BREAK to stop when signal is off. If “3 wires” was chosen, use YES or NO
to answer the prompt on the display and choose among “push-to-run” or “latched
instant reverse” control modes. If “2 wires” was chosen, use YES and NO to choose
among “open if signal ON” or “open if signal OFF” control modes.
9.1.5
Local Controls
This routine allows:
•
To configure the control mode by means of the local controls when the 3-position
selector is in LOCAL. The available options are “push-to-run”, “latched”, “latched
with instant reverse”.
•
To set the LED’s color. The following options are available: open LED: green or red;
close LED: green or red; alarm LED: yellow or red.