September 2021
Installation, Operation and Maintenance Manual
VCIOM-01249-EN Rev. 0
55
Set-Up Routines
Section 9: Set-Up Routines
Configuration procedure
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and then enter the password according to the instructions
(see “Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press YES to select actuator set-up menu, press NO to scroll the
list of available routines and then press YES to select ESD set-up.
•
Press YES if the ESD action is correct or press NO to scroll the list of available
options (off, open, close, stay-put, go to position xx %). Press YES to select the
desired option.
•
Press either YES or NO to select the signal type (present, absent).
•
Press YES to change ESD priority with reference to the following signals or status:
—
(*) Motor thermostat alarm. Choosing ESD > THERMOSTAT, the ESD
action will be carried out also in case of motor over-heating. Vice-versa,
if ESD < THERMOSTAT was chosen, the ESD action will not be done in case
of motor over-heating.
—
(*) Torque limit tripped. Choosing ESD > TORQUE LIMIT, the ESD
action will be carried out also in case of torque alarm. Vice-versa,
if ESD < TORQUE LIMIT was chosen, the ESD action will not be done in
case of torque alarm.
—
(*) Local stop pressed. Choosing ESD > LOCAL STOP, the ESD action
will override the local STOP signal. Vice-versa, if ESD < LOCAL STOP was
chosen, the ESD action will not be performed if the local STOP pushbutton
is pressed.
—
Local selector in LOCAL. Choosing ESD > LOCAL CONTROLS, the
ESD action will be carried out also when the local selector is in LOCAL.
Vice-versa, if ESD < LOCAL CONTROLS was chosen, the ESD action will not
be performed if the 3-position selector is in LOCAL.
—
2-speed timer. Choosing ESD > 2-speed timer, the 2-speed timer function
will be inhibited during ESD action. Vice-versa, if ESD < 2-speed timer was
chosen, the 2- speed timer function will be active during ESD action.
—
(*) Local selector in OFF. By choosing ESD > OFF, the ESD action
will be carried out also when the local selector is in OFF. Vice-versa,
if ESD < OFF was chosen, the ESD action will not be performed if the
3-position selector is in OFF.
The factory configuration is the following: action: CLOSE, signal type: PRESENT, priorities:
ESD > LOCAL CONTROLS, ESD > 2-SPEED TIMER, ESD < all other cases.