September 2021
Installation, Operation and Maintenance Manual
VCIOM-01249-EN Rev. 0
57
Set-Up Routines
Section 9: Set-Up Routines
Configuration procedure
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and then enter the password according to the instructions
(see “Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press YES to select the actuator set-up menu, press NO to scroll
the list of available routines and then press YES to select Local controls.
•
Press YES to change control mode or press NO to proceed to LED’s color setting.
Control mode
Press YES if the display shows the correct control mode or press NO to scroll the list of
available options (push-to-run, latched). Press YES to confirm. Option "push-to-run rel.
AS5-6" is used when a remote enabling of local commands is required. With the local
selector in LOCAL, pressing the OPEN or CLOSE local pushbuttons causes relays AS5 or AS6
to switch, but no command is sent to motor. The control PLC should read the status of the
above-mentioned relays and send an open or close command on the remote inputs (see
Section 5.6 push-to-run mode; see relevant electrical diagram when the option is used).
LED’s color
•
Press YES if the color of the open LED is correct. Press NO to change it, then YES
to confirm.
•
Press YES if the color of the close LED is correct. Press NO to change it, then YES
to confirm.
•
Press YES if the color of the alarm LED is correct. Press NO to change it, then YES
to confirm.
9.1.6
Output Relays
Monitor relay
The voltage-free, change-over, contacts of the monitor relay indicate that the actuator
is either available for remote control or that a problem or a condition preventing remote
control of the valve exists.
The monitor relay is normally energized and will be de-energized on:
•
main voltage failure
•
lost phase
•
internal temperature alarm
•
K1 contactor failure
•
K2 contactor failure
•
position sensor failure
•
speed sensor failure
•
configuration error
•
HW error
•
mid-travel alarm