View Routines
Section 10: View Routines
View procedure
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language according to the instructions (see “Entering the view mode”).
When the message displayed is “VIEW MODE OK?” press YES. Press NO to scroll
the list of available menus and press YES to select the Maintenance menu.
•
Press NO to scroll the list of available routines and press YES to select
operation log.
•
Press YES to select general data or press NO to skip to recent data.
•
Press YES to scroll the list of values.
•
Press YES to view the recent data log or press NO to exit.
•
Press YES to scroll the list of values.
Table 15.
General Data
Opening time
This datum is only available in the general data log. It is updated at the end of every full
valve stroke of the valve in opening direction. The data of the previous stroke are lost.
It gives the time necessary to the valve to move from the close position to the open
position, expressed in hours, minutes and seconds.
Closing time
This datum is only available in the general data log. It is updated at the end of every full
valve stroke of the valve in closing direction. The data of the previous stroke are lost.
It gives the time necessary to the valve to move from the open position to the close
position, expressed in hours, minutes and seconds.
Contactor cycles
This number counts the cycles of contactors K1 and K2. The value indicated in the
general data log is also used to generate the “max. contactor cycles” warning when the
maximum allowable number of cycles of the contactor is reached (see Section 12.10,
Diagnostic messages). If the main power is DC or single phase and in modulating
actuators, the counters (general and recent) are hold to 0.
Motor run time
This number counts the hours with motor energized.
No power time
This number counts the hours without electrical power.
Utilization rate
This number % is incremented every 200 full strokes of the actuator. It reaches 100%
after 20 000 full strokes.
Temperature min
This is the lowest temperature value (in °C) measured inside the electronics
compartment.
Temperature max
This is the highest temperature value (in °C) measured inside the electronics
compartment.
Term temp min
This is the lowest temperature value (in °C) measured inside the terminal board
enclosure.
Term temp max
This is the highest temperature value (in °C) measured inside the terminal board
enclosure.
Motor temp max
This is the highest temperature value (in °C) measured in the electrical motor.
Thermostat alarms
This counts the number of alarms due to the high temperature of the electrical motor
and to the tripping of the motor thermostat.
Torque alarms
This counts the number of alarms due to high torque in opening and closing.