September 2021
Installation, Operation and Maintenance Manual
VCIOM-01249-EN Rev. 0
40
Local Controls
Section 6: Local Controls
5.
Three LED’s
to indicate the actuator status according to the following logic:
—
green ON/ red OFF: the actuator is stopped in open position
—
green OFF/ red ON: the actuator is stopped in closed position
—
green OFF/ red flashing: the actuator is running in closing direction
—
green flashing/ red OFF: the actuator is running in opening direction
—
green ON/ red ON: the actuator is stopped in intermediate position
—
yellow ON: alarm
—
yellow flashing: warning
The above color combination is supplied as standard, but it may be changed (red
with green, green with red, and yellow with red), during actuator setting operations.
6.
Local controls
: OPEN/YES, CLOSE/NO, and STOP pushbuttons. The STOP
pushbutton resets any existing command and is active both in local and remote.
If the 3-position selector is in LOCAL, the OPEN / YES, and CLOSE /NO pushbuttons
work as OPEN and CLOSE commands.
If the 3-position selector is in REMOTE or in OFF, the OPEN / YES and CLOSE / NO
pushbuttons work as YES and NO to answer the prompt (next? OK? view?, change?
exit?) of the alphanumeric display.
In OFF, the OPEN / YES and CLOSE / NO pushbuttons allow to scroll down the
menu, to view and change the actuator configuration or to scroll the list of
variables, status, and alarms.
In REMOTE, the above pushbuttons allow scrolling the list of variables, status,
alarms and reports but the actuator configuration cannot be viewed or changed.