September 2021
Installation, Operation and Maintenance Manual
VCIOM-01249-EN Rev. 0
79
View Routines
Section 10: View Routines
Section 10: View Routines
10.1
Actuator Set-Up
The above menu allows to view the present actuator configuration. No change can be
made to the present data. The following data can be viewed (see Table 12).
Routine
Parameters
Stroke limits
Close direction (CW, CCW), close limit type (torque or position),
open limit type (torque or position)
Torque set-up
Closing torque limit %, opening torque limit %
ESD controls
ESD action, signal type, ESD priority
Remote controls
Control type
Locals controls
Control type, LED’s color
Output relays
Monitor relay conditions, ASi conditions, contact action
Positioner *
Dead band, motion inhibit time, polarity, %min, %max
(%min and %max are present only if “position request R%” is from
4 - 20 mA input)
Fail-safe *
Action, delay
Out 4 - 20 mA *
Output signal (position or torque), polarity
Interlock
Signal type in OP, signal type in CL
2-speed timer
Close direction: status, start, stop, on time, off time
Open direction: status, start, stop, on time, off time
Bus *
Node address, terminations, etc. depending on fieldbus type
Miscellaneous
Time and date, torque mode, lithium battery, torque bypass %,
valve jammed time
Table 12.
NOTE:
The routines with * can only be viewed if the relevant electronic cards are present. If the bus interface is
LonWorks, routine “BUS” changes to “FDI control”. Detailed descriptions of the above routines and their
parameters can be found in Section 9.
View procedure
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language according to the instructions (see “Entering the view mode”).
When the message displayed is “VIEW MODE OK?” press YES. Press YES to select
the actuator set-up menu.
•
Press NO to scroll the list of available routines and press YES to select.
•
Press YES to answer at the prompt “view” or “next” and to see the data.