September 2021
Installation, Operation and Maintenance Manual
VCIOM-01249-EN Rev. 0
89
View Routines
Section 10: View Routines
Figure 54 shows a graph with sampling time 1 sec in T-RECORDER mode after a recording
stop for OVER-TORQUE alarm:
1.
Torque limit in OP reached
2.
Curve selector:
—
Torque
—
Motor temperature
—
Main voltage
Torque limit in CL is set to 90%, torque limit in OP is set to 100%. Blue graph shows
Torque OP versus time, yellow graph shows Torque CL versus time. The data remain in the
F01-2000 v4 permanent memory until a new start of data logger is set.
Figure 54
1
2