September 2021
Installation, Operation and Maintenance Manual
VCIOM-01249-EN Rev. 0
69
Set-Up Routines
Section 9: Set-Up Routines
9.1.13.2
Factory Settings
The above routine resets the present configuration and restores the default configuration
as below:
Stroke limits
Close direction: CW
Close limit: by position
Open limit: by position
Torque set-up
Closing torque: 40%
Opening torque: 40%
ESD set-up
ESD action: close
ESD signal: present ESD priority:
-
ESD < motor thermostat
-
ESD < torque limit
-
ESD < local stop
-
ESD > local controls
-
ESD > 2-speed timer
-
ESD < OFF
Remote controls
Control type: 4 wires latched
Locals controls
Control type: latched with instant reverse
LED’s color:
-
green = open / opening
-
red = close / closing
-
yellow = alarm / warning
Output relay
Default #1
2-speed timer
Opening direction: off
Closing direction: off
Miscellaneous
Lithium battery: absent
Torque profile: standard
Torque bypass: 4%
Valve jammed: 4 sec
Table 11.
Configuration procedure
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and then enter the password according to the instructions
(see “Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press YES to select the actuator set-up menu, press NO to scroll
the list of available routines and then press YES to select Miscellaneous.
•
Press No to scroll the list of routines and press YES to select factory configuration.
Press YES to download the standard configuration, press NO to exit.