Set-Up Routines
Section 9: Set-Up Routines
Default #2
Monitor relay
•
main voltage failure
•
lost phase
•
local/off selected
•
local stop pressed
•
manual operation
•
internal temperature alarm
•
K1 contactor failure
•
K2 contactor failure
•
position sensor failure
•
speed sensor failure
•
configuration error
•
HW error
•
motor over-temperature
•
over-torque
•
jammed valve
•
low lithium battery (if present)
•
mid-travel alarm
Auxiliary relays
AS1: open limit; break
AS2: close limit; break
AS3: position >90%; break
AS4: position <5%; break
AS5: motor running; make
AS6: remote selected; make
AS7: warning; make
AS8: local selected
Configure output relays
Press YES to change the monitor relay or NO to change auxiliary relays AS1, 2, 3, 4, 5, 6,
7, and 8.
Monitor relay
Press YES or NO to enable or disable the following situations from the conditions which
de-energize the monitor relay: motor over-temperature, over-torque, jammed valve,
manual override, ESD signal on, low lithium battery (if present), local STOP pressed,
LOCAL/OFF selected.