September 2021
Installation, Operation and Maintenance Manual
VCIOM-01249-EN Rev. 0
77
Set-Up Routines
Section 9: Set-Up Routines
9.3.7
Set Data Logger
The “data logger” routine allows to set the data logger parameters (see VIEW mode,
Maintenance, Data logger, Section 10.4.6). To start the data logger, the following data
should be set:
Logger mode
recorder, event, off
Sampling time
from 1 to 3600 s (the sampling time is only used in recorder mode)
Memory mode
stop when memory is full, continuous (stop after overwriting the
memory 5000 times (event) and 10000 times (recorder/T-recorder)
Start date
date when the logger starts
Start time
time when the logger starts
Configuration procedure
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and then enter the password according to the instructions
(see “Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press NO to scroll the list of available menus and then press YES to
select maintenance menu.
•
Press NO to scroll the list of available routines and then press YES to select
“data logger”.
•
Press YES if the mode is correct. Press NO to scroll the list of modes and press YES
to select the desired value.
•
Press YES if the sampling time is correct. Press NO to scroll the list of times and
press YES to select the desired value.
•
Press YES if the memory mode is correct (stop when full or continuous). Press NO
to change and press YES to select.
•
Press YES if the start time is correct. Press NO to scroll the list and press YES to
select the desired sampling times (hour, min, sec).
•
Press YES if the start date is correct. Press NO to scroll the list and press YES to
select the desired sampling times (day, month, year).
•
Press YES to confirm the above settings.