Set-Up Routines
Section 9: Set-Up Routines
Section 9: Set-Up Routines
9.1
Actuator Set-Up
9.1.1
Set Stroke Limits
This routine allows the actuator to be configured according to the type of valve it is
mounted on.
The following parameters will be set:
•
Opening and closing torque limits: from 40% to 100% of the nominal torque.
The nominal torque corresponding to 100% is set in-house and is stated in the
nameplate menu for reference.
•
Close direction: clockwise (CW) or counterclockwise (CCW). Most valves require
clockwise rotation of the stem when viewed from the handwheel. Engage the
manual override and check if the valve closes with clockwise or counterclockwise
rotation of the handwheel.
•
Close and open limits type: by position or by torque. Use the table below
to choose.
Set-up procedure
•
Engage the manual override and move the valve to the mid-travel position.
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and then enter the password according to the instructions
(see “Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press YES to select the actuator set-up menu, and then press YES
again to start with the stroke limits routine.
•
Press YES if the closing torque limit is correct or NO to scroll the list of available
values. When the value is correct, press YES.
•
Press YES if the opening torque limit is correct or NO to scroll the list of available
values. When the value is correct press YES.
•
Press YES if the rotation to close is correct (CW or CCW), or NO to change.
When the value is correct press YES.
•
Press YES to set the close limit, or NO and then YES to set the open limit.
Close limit type
Press YES if the close limit type is correct (torque or position), press NO to change it.
Press YES when the type is correct.