2–21
Application - 2
Save
Cancel
@ : WARNING, Function DISABLED until output selected!
(46) - NEGATIVE SEQUENCE OVERCURRENT
Pickup:
Delay:
Def. Time
OUTPUT
8
7
6
5
4
3
2
1
FL
6
5
4
3
2
1
Blocking Input
@
0.10 Amp
1 Cycle
20.00 Amps
8160 Cycles
Pickup:
Delay:
Inv. Time
OUTPUT
8
7
6
5
4
3
2
1
FL
6
5
4
3
2
1
Blocking Input
@
Curves
Definite Time
IECI
Inverse
IECVI
Very Inverse
IECEI
Extremely Inverse
IECLTI
0.50 Amp
0.5
5.00 Amps
11.0
Figure 2-12
M-3822 IPScom
®
for Windows™ Negative Sequence Overcurrent (46) Setpoint
Ranges
Path
: Relay Menu/Setup/Setpoints/(46) Negative Sequence Overcurrent
COMMAND BUTTONS
Save
Saves all information to the relay.
Cancel
Returns the user to the previous window; any changes to the displayed information are lost.