M-3520 Instruction Book
6–42
7.
Timer Test:
Reset targets and apply Nominal Voltage to all three phases at a sweep rate 25% below
P
. With output contacts connected to a timer, apply a sweep rate 25% above
P
and start timing. The
contacts will close after
D
cycles within –1 to +3 cycles, or
&
3 %.
8.
If testing is complete, enable any functions disabled for this test. If further testing is desired, check
the proper functions to disable for the next test and continue from this point.