–4–
M-3520 Intertie Protection Relay
STANDARD FUNCTIONS (
cont.)
Device
Setpoint
Number
Function
Ranges
Increment
Accuracy
†
Instantaneous Phase Overcurrent
Instantaneous Phase Overcurrent
Instantaneous Phase Overcurrent
Instantaneous Phase Overcurrent
Instantaneous Phase Overcurrent
Pickup
1.0 to 240.0 A
0.1 A
&
0.1 A or
&
3%
(0.2 to 48.0 A)
(
&
0.02 A or
&
3%)
Time Delay
2 Cycles
—
&
2 Cycles
Instantaneous Neutral Overcurrent
Instantaneous Neutral Overcurrent
Instantaneous Neutral Overcurrent
Instantaneous Neutral Overcurrent
Instantaneous Neutral Overcurrent
Pickup
0.5 to 240.0 A
0.1 A
&
0.1 A or
&
3%
(0.1 to 48.0 A)
(
&
0.02 A or
&
3%)
Time Delay
2 Cycles
—
&
2 Cycles
The 50G can be supervised by the ground directional element (if 67N option is selected).
Inverse Time Neutral Overcurrent
Inverse Time Neutral Overcurrent
Inverse Time Neutral Overcurrent
Inverse Time Neutral Overcurrent
Inverse Time Neutral Overcurrent
Pickup
0.25 to 12.00 A
0.01 A
&
0.1 A or
&
3%
(0.05 to 2.40 A)
(
&
0.02 A or
&
3%)
Characteristic Curve
Definite Time/Inverse/Very Inverse/Extremely Inverse/IEC Curves
Time Dial
0.5 to 11.0
0.1
&
3 Cycles or
&
5%
0.05 to 1.10 (IEC curves)
0.01
The 51G can be supervised by the ground directional element.
Inverse Time Overcurrent, with Voltage Control or Voltage Restraint
Inverse Time Overcurrent, with Voltage Control or Voltage Restraint
Inverse Time Overcurrent, with Voltage Control or Voltage Restraint
Inverse Time Overcurrent, with Voltage Control or Voltage Restraint
Inverse Time Overcurrent, with Voltage Control or Voltage Restraint
Pickup
0.50 to 12.00 A
0.01 A
&
0.1 A or
&
3%
(0.10 to 2.40 A)
(
&
0.02 A or
&
3%)
Characteristic Curve
Definite Time/Inverse/Very Inverse/Extremely Inverse/IEC Curves
Time Dial
0.5 to 11.0
0.1
&
3 Cycles or
&
5%
0.05 to 1.10 (IEC curves)
0.01
Voltage Control (VC)
5 to 180 V
1 V
&
0.5 V or
&
5%
or
Voltage Restraint (VR)
Linear Restraint
—
—
Overvoltage
Overvoltage
Overvoltage
Overvoltage
Overvoltage
Pickup #1, #2
5 to 180 V
1 V
&
0.5 V or
&
0.5%
&
0.8 V or
&
0.75%*
Time Delay #1, #2
1 to 8160 Cycles
1 Cycle
–1 to +3 Cycles or
&
1%
* When line-ground to line-line is selected.
Neutral Overvoltage
Neutral Overvoltage
Neutral Overvoltage
Neutral Overvoltage
Neutral Overvoltage
Pickup
5 to 180 V
1 V
&
0.5 V or
&
0.5%
Time Delay
1 to 8160 Cycles
1 Cycle
–1 to +3 Cycles or
&
1%
Peak Overvoltage
Peak Overvoltage
Peak Overvoltage
Peak Overvoltage
Peak Overvoltage
Magnitude
1.05 to 1.50 PU
0.01 PU
&
0.03 PU*
Time Delay
1 to 8160 Cycles
1 Cycle
–1 to +3 Cycles or
&
1%
Instantaneous voltage magnitude response; intended for ferroresonance protection.
*For fundamental (60 Hz/50 Hz) signal only. For distorted input signals, the accuracy degrades as the
order of the harmonic signal increases. The accuracy applies to voltages below 180 V.
†
Select the greater of these accuracy values.
Values in parentheses apply to 1 Amp CT secondary rating.
50
50G
51G
59
51V
59G
59I
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...