59I Peak Overvoltage, 3-Phase
VOLTAGE INPUTS:
V1
CURRENT INPUTS:
None
TEST SETTINGS:
Pickup
P
1
PU
(1.05 to 1.50)
Time Delay
D
Cycles
(1 to 8160)
Programmed Outputs
Z
Output
(1 to 8)
Functions 59, 79
Disable
■
■
■
■
■
NOTE:
If function 59 settings are greater than the 59I setting being tested, it is not necessary to disable.
1.
Disable functions as shown. Refer to Section 3.2, Configure Relay Data, for procedure.
2.
Confirm settings to be tested.
3.
Connect inputs in Configuration V1 designated above. Refer to Section 6.1, Equipment/Test Setup
for configuration. Set voltages to Nominal Voltage.
4.
Pickup Test
: Hold the
TARGET RESET
button in, and slowly increase the voltage applied to Phase
A until the
59I PEAK OVERVOLTAGE
LED goes on or the pickup indicator operates on the
computer target screen. The level should be equal to
P
PU
&
0.3 PU. Release the
TARGET RESET
button and decrease the input voltage and the
OUTPUT
LEDs will go out. Press
TARGET RESET
button to remove targets. This test may be performed on each phase, if desired.
5.
Time Test
: With output contacts being connected to the timer, apply (
P
+5) Volts and start timing.
The contacts will close after
D
cycles within –1 to +3 cycles.
6.
If testing is complete, enable any functions disabled for this test. If other tests are to be completed,
check the proper functions to disable for the next test and proceed from this point.
1
Accuracy of the function only applies to voltages below 180 Volts.
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...