2–42
M-3520 Instruction Book
78 DIAMETER
________ Ohms
78 OFFSET
________ Ohms
78 BLINDER IMPEDANCE
________ Ohms
78 IMPEDANCE ANGLE
________ Degrees
78 DELAY
________ Cycles
78 TRIP ON MHO EXIT
disable enable
78 POLE SLIP COUNT
________ slips
78 POLE SLIP RESET TIME
________ Cycles
A negative or positive offset can be specified to offset
the mho circle from the origin.
The blinder impedance should be programmed less
than the set diameter.
Circle Diameter:
Offset:
Pole Slip Reset Time:
Impedance Angle:
Blinder Impedance:
Delay:
Pole Slip Counter:
@ : WARNING, Function DISABLED until output selected!
(78) - OUT OF STEP
Trip on MHO Exit:
Enable
Disable
Save
Cancel
0.1 Ohms
- 100.0 Ohms
1 Cycle
0 Degree
0.1
1 Cycle
1
100.0 Ohms
100.0 Ohms
8160 Cycles
90 Degrees
50.0
8160 Cycles
20
#1
OUTPUT
8
7
6
5
4
3
2
1
FL
6
5
4
3
2
1
Blocking Input
@
Figure 2-30
M-3822 IPScom® for Windows™ Out-of-Step (78) Setpoint Ranges