M-3520 Instruction Book
6–2
6.1
Equipment and Test Setup
The M-3520 Intertie Protection Relay has been
calibrated and fully tested at the factory. If calibration
is necessary because of component replacement,
follow the Auto-Calibration Procedure described in
Section 6.3.
Automatic Calibration
■
■
■
■
■
NOTE
: If necessary, refer to Figures 6-2, 6-3,
and 5-4 for reference to the
HMI
and
TARGETS
controls and LEDs, and rear
connections.
Required Equipment
The following equipment is required to carry out the
test procedures:
•
Two Digital Multi-meters (DMM) with a 10
Amp current range. These are not required
if using a Pulsar Universal Test System.
•
One power supply for the relay, capable of
supplying 120 V ac or 125 V dc for units
with high voltage power supplies, or 24 V
dc for units with Low Voltage power
supplies.
•
One 3-phase voltage source capable of 0
to 250 V ac. (Pulsar Universal Test System
or equivalent.)
•
One 3-phase current source capable of 0 to
25 Amps. (Pulsar Universal Test System
or equivalent.)
•
Electronic timer with a minimum accuracy
of 8 ms. (Pulsar Universal Test System or
equivalent.)
■
■
■
■
■
NOTE:
A single-phase frequency tester may be
used: 48 to 59.99 Hz for 60 Hz units; 38 to
49.99 Hz for 50 Hz units
Equipment Setup
▲
▲
▲
▲
▲
CAUTION:
The proper voltage range for the relay
is clearly marked underneath each of the power
supply inputs.
1.
Connect power to the relay’s power input
terminals 62 and 63. The M-3520 may be
configured with a high voltage power
supply with a nominal voltage input of
110/120 /230/240 V ac or 110/125/220/
250 V dc. The relay is also available with
a low voltage power supply with nominal
voltage input of 24/48 V dc, and a
redundant power supply, which is available
as an option.
2.
Connect the voltage and current inputs for
each test procedure according to the
configuration included with each test
description and follow the outlined steps.
It is recommended to disable any
functions that may operate while
performing tests on a particular function.
3.
Table 6-1 identifies the functions to
disable.
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...