–9–
M-3520 Intertie Protection Relay
Control/Status Inputs
The control/status inputs, INPUT1 through INPUT6, can be programmed to block any of the relay functions,
trigger the oscillographic recorder or operate one or more outputs. The control/status inputs are designed to
be connected to dry contacts and are internally wetted with a 24 V dc power supply. To provide breaker
status LED indication on the front panel, the INPUT1 control/status input contact should be connected to the
52b breaker status contact.
Output Contacts
The eight programmable output contacts (six form ‘a’ and two form ‘c’), the power supply alarm output
contact (form ‘b’), and the self-test alarm output contact (form ‘c’) are all rated as per ANSI/IEEE
C37.90-1989 for tripping: make 30 A for 0.2 seconds, carry 8 A, break 6 A @ 120 V ac, break 0.1 A @ 125
V dc, inductive break 0.1 A.
Any of the relay functions can be individually programmed to activate any one or more of the eight
programmable output contacts.
Target/Status Indicators and Controls
The
RELAY OK
LED reveals proper cycling of the microcomputer. The
BRKR CLOSED
LED illuminates when
the breaker is closed (when the 52b contact is open). The
OSC TRIG
LED indicates that oscillographic data has
been recorded in the unit's memory. The corresponding
TARGETS
LED will illuminate when any of the relay
functions trip. Pressing and releasing the
TARGET
RESET
pushbutton resets the
TARGET
LED if the
conditions causing the operation have been removed. Pressing and holding the
TARGET RESET
pushbutton
will allow elements or funcitons in pickup to be displayed. The
PS1
and
PS2
LEDs remain illuminated as long
as power is applied to the unit and the power supply is operating properly. The
TIME SYNC
LED will illuminate
when a valid IRIG-B signal is applied, and time synchronization has been established.
Communication
Communications ports include rear panel RS-232 and RS-485 ports, a front panel RS-232 port, and an IRIG-B
port. The communications protocol implements serial, byte-oriented, asynchronous communication, and
provides the following functions when used with the Microsoft
®
Windows™ compatible M-3822 IPScom
®
Communications Software package. MODBUS and BECO 2200 protocols are supported using:
•
Setpoint interrogation and modification
•
Time-stamped trip target information for the 32 most recent events
•
Real time metering of all quantities measured
•
Downloading of recorded oscillographic data (not available with MODBUS protocol)
IRIG-B
The relay can accept either modulated or demodulated IRIG-B time clock synchronization signal. The IRIG-B
time synchronization information is used to correct the hour, minutes, seconds and milliseconds information.
Human-Machine Interface (HMI) Module (optional)
Local access to the relay is provided through an optional M-3931 HMI Module, allowing for easy to use,
menu-driven access to all functions via a 6-button keyboard and a 2-line by 24 character alphanumeric
display. Features of the HMI Module include the following:
•
User-definable access codes providing three levels of security
•
Interrogation and modification of setpoints
•
Time-stamped trip target information for the 32 most recent events
•
Real-time metering of all quantities measured
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...