M-3520 Instruction Book
6–16
7.
Delta Voltage Test
: Set the Upper and Lower Voltage limits to their maximum and minimum values,
respectively. Set V2 to 140 V and V1 to 80 V. Hold the
TARGET RESET
button in and slowly
increase the voltage on V1 until Output
Z
LED operates, or the pickup indicator operates on the
computer target screen. The voltage difference should be equal to
&
0.5 V. Release the
TARGET
RESET
button, and decrease the voltage, and the
OUTPUT
LED will go out. If desired, repeat the
test using V2 with V1 at 140 volts.
8.
Delta Frequency Test:
Set V1 and V2 to Nominal Voltage, and set the frequency of V1 to 0.05 lower
than Nominal Frequency –
DF
. Hold the
TARGET RESET
button in, and slowly increase the
frequency of V1 until Output
Z
LED operates, or the pickup indicator operates on the computer target
screen. The frequency difference level should be equal to
DF
&
0.0007 Hz or 5%. Release the
TARGET RESET
button and decrease the frequency, and the
OUTPUT
LED will go out. If desired,
repeat the test using V2 with V1 at Nominal Frequency.
9.
Dead Volt Limit Test:
Dead V1 Test
: Enable Dead V1 and disable Dead V2 (if enabled). Set V2 to Nominal Voltage, and V1
to
DVL
+5 V. Hold the
TARGET RESET
button in, and slowly decrease the voltage on V1 until
Output
Z
LED operates, or the pickup indicator operates on the computer target screen. The voltage
level should be equal to
DVL
&
0.5 V or
&
5%. Release the
TARGET RESET
button and increase
the voltage level and the
OUTPUT
LED will go out.
Set V1 to Nominal Voltage, and decrease V2 below
DVL
and verify that the function does not
operate.
Dead V2 Test:
Enable Dead V2 and disable Dead V1 (if enabled). Set V1 to Nominal Voltage, and V2
to
DVL
+5 V. Hold the
TARGET RESET
button in, and slowly decrease the voltage on V2 until
Output
Z
LED operates, or the pickup indicator operates on the computer target screen. The voltage
level should be equal to
DVL
&
0.5 V or
&
5%. Release the
TARGET RESET
button and increase
the voltage level and the
OUTPUT
LED will go out.
Set V2 to Nominal Voltage, and decrease V1 below
DVL
, and verify that the function does not
operate.
Dead V1 and V2 Test
: Enable Dead (V1 & V2) . Disable Dead (V1) and Dead (V2), if enabled. Set V1
and V2 to
DVL
+5 V. Hold the
TARGET RESET
button in, and slowly decrease the voltage on V1
and V2 until Output
Z
LED operates, or the pickup indicator operates on the computer target screen.
The voltage level should be equal to
DVL
&
0.5 V or
&
5%. Release the
TARGET RESET
button and
increase the voltage level and the
OUTPUT
LED will go out.
Set V1 to Nominal Voltage, decrease V2 below
DVL
, and verify that the function does not operate.
Set V2 to Nominal Voltage, decrease V1 below
DVL
, and verify that the function does not operate.
10.
Dead Input Enable Test
: Select one of the Dead Inputs (
DIN
) and activate it. Repeat step 9, verify
that the function operates as in step 9. Deactivate the
DIN
and repeat step 9 once more. Verify that
the function does not operate. Disable Dead Input feature when this step is complete.
11.
Dead Timer Test:
Enable Dead V1 & V2. Disable Dead V1 and Dead V2 (if enabled). Set V1 and V2
to
DVL
+5 V. With output contacts connected to a timer, remove V1 and V2 and start timing. The
contacts will close within –1 to +3 cycles or
&
1%.
12.
If testing is complete, enable any functions disabled for this test. If further testing is desired, check
the proper functions to disable for the next test and continue from this point.
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...