M-3520 Instruction Book
6–18
27G Undervoltage, Neutral
VOLTAGE INPUTS:
See Below
CURRENT INPUTS:
None
TEST SETTINGS:
Pickup
P
Volts
(5 to 180)
Time Delay
D
Cycles
(1 to 8160)
Programmed Outputs
Z
OUT
(1 to 8)
Functions 59G, 79
Disable
1.
Disable functions as shown. Refer to Section 3.2, Configure Relay Data, for procedures.
2.
Confirm settings to be tested.
3.
Connect voltage input to V
G
, terminals 41 & 42. Set at 105% of Pickup
P
.
4.
Pickup Test
: Hold the
TARGET RESET
button in and slowly decrease the neutral voltage until
27G
NEUTRL UNDERVOLTAGE
LED illuminates, or the pickup indicator operates on the computer
target screen. The level should be equal to
P
volts
&
0.5V or
&
5%. Release the
TARGET RESET
button and increase the input to the nominal voltage and the
OUTPUT
LED will extinguish. Press
TARGET RESET
button to remove targets.
5.
Time Test
: With output contacts connected to the timer, apply (
P
-1) Volts and begin timing. The
contacts will close after
D
cycles within –1 or +3 cycles or
&
1%.
6.
If testing is complete, enable any functions disabled for this test. If further testing is desired, check
the proper functions to disable for the next test and continue from this point.
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...