CS1 Single Phase SSR Quick Start Manual

 0037-75553 (PK527)

This manual is intended to provide only the basic installation and operation instruc-

tions for the CS1 Single Phase Solid State Relay. Please refer to manual, PK521, for 

complete installation & operation details. The most current revision of PK521 may be 

found on the Chromalox website: www.chromalox.com

 1. IMPORTANT SAFEGUARDS

ELECTRIC SHOCK HAZARD: Read and understand all instructions before 

installing, servicing or operating this controller. Failure to do so could 

result in equipment or property damage as well as personal injury and 

even death.

HIGH VOLTAGE is used in the operation of this equipment. DEATH ON 

CONTACT may result if personnel fail to observe safety precautions. 

Learn the areas containing high-voltage connections when installing or 

operating this equipment.

Be careful not to contact high-voltage connections when installing or 

operating this equipment. Before working inside the equipment, turn 

power off and ground all points of high voltage potential before touch-

ing.

ELECTRIC SHOCK HAZARD. Any installation involving control equip-

ment must be performed by a qualified person and must be effectively 

grounded in accordance with the National Electrical Code to eliminate 

shock hazard. 

The Owner/Installer must provide all necessary safety and protection 

devices and follow all current electrical wiring standards and regula-

tions. Failure to do so may compromise the integrity of the controller 

and/or cause product failure resulting in a safety risk to operational 

service and personnel.

This controller utilizes a heat sink which is designed to cool the unit 

during operation. Under no circumstance should air flow around the 

controller be compromised in any way. Failure to do so may result in the 

overheating of the controller, product failure, product temperatures and 

even fire.

During continuous operation, the heat sink can reach a very high tem-

peratures, and keeps a high temperature even after the unit is turned 

off due to its high thermal inertia.
Higher voltages may be present. DO NOT work on the power section 

without first disconnecting electrical power to the panel. Failure to do 

so could result in serious injury or death.

 2. INSTALLATION - MECHANICAL

To ensure proper performance, maximum safety and reliability, it is essential to install 

the unit correctly. This includes proper mounting, spacing, hardware and wiring. See 

below:
1.  Maximum surrounding air temperature is 40°C in “Open Type Equipment” which 

is suitable for use in pollution degree 2.

2.  Install the unit vertically (max 10° inclination from vertical axis).

3.  Spacing:

  –Min. vertical distance between unit and panel wall: 3.9” (100 mm)

  –Min. horizontal distance between unit and panel wall: 0.79” (20 mm)

  –Min. vertical distance between adjacent power control units: 11.81” (300 mm)

  –Min. horizontal distance between adjacent power control units: 0.79” (20 mm)

 3. INSTALLATION – ELECTRICAL

Control Signal Input

Dimensions & Weights

Control Terminal Description – CS1 Models > 40 Amps

Terminal

Description

24VDC Input Signal (Type 1)  

(6 – 32 VDC)

VAC/DC Input Signal 

(Type 2)

(20 – 260 VAC/DC)

1

Not Used

2

Control Signal Input

& VDC Power Supply

Control Signal Input (-)

& Optional -24 VDC Power Supply Input

VAC/DC INPUT

3

Control Signal Input

Control Signal Input (+)

4

VDC Power Supply

Op24 VDC Power Supply Input

Not Used

5

Not Used

6

Alarm Output

Alarm Options 1 & 2:  

Solid State Switch

Alarm Options 3 & 4:  

Internally connected to 

Terminal #4 (+VDC Power 

Supply)

Alarm Option 1:

Solid State Switch

7

Alarm Output

Alarm Options 3 & 4:  

PNP Digital Signal Output

8

Not Used

Depth =  5.6” (142)

Weight = 2.9 lb (1300 g)

               3.7 lb (1700 g)

Depth     =      4.2” (107)                5.6” (142)                       5.6” (142)                               5.6” (142)

Weight   =   .71 lb (320 g)          1.2 lb (540 g)                1.9 lb (900 g)                        2.6 lb (1200 g)

(without fan)
(without fan)
(with fan)

1.97” (50) max.

1.18” (50)

5” (127)

3.15” (80)

2.36” (60)

1.4” (35)

.95” (24)

3.94” (100)

4.24” (108)

0.5” (14)

0.7” (18)

CS1 25 A

CS1 40 A

CS1 50 A

CS1 60 A

CS1 75 A
CS1 90 A
CS1 120 A

CS1 

CS1 

CS1 

CS1 

CS1 

LED 1 

Red: Input Control Signal Present

Yellow: Overtemperature Condition,

Input Control Signal Present

Blank: No Input Control Signal

 

LED 2 (Optional)

Red:    Alarm Output Active
Blank:  No Alarm Output 

LOAD

2 /T1

LINE
1 /L1

GROUND

1     2     3     4     5     6     7     8     

+

Control Signal 

Input     –

24 Vdc or 

20 - 260 Vac/dc

25 & 40 Amp 

50 -120 Amp 

ON  (Red)

 

OVER TEMP  (Yellow)

AL

Optional

External - 24 Vdc Power Supply

Ex24 Vdc Power Supply
Alarm Output

See Wiring 

Alarm Output

Diagrams

2         3

 

ON

LOAD

2 /T1

LINE 
1 /L1

GROUND

+

Control & Power

Connections

LEGACY PRODUCT

Summary of Contents for CS1

Page 1: ...connecting electrical power to the panel Failure to do so could result in serious injury or death 2 INSTALLATION MECHANICAL To ensure proper performance maximum safety and reliability it is essential to install the unit correctly This includes proper mounting spacing hardware and wiring See below 1 Maximum surrounding air temperature is 40 C in Open Type Equipment which is suitable for use in poll...

Page 2: ...rves reflect units tested complete with approved heat sinks and fans if applicable 30 25 10 5 10 15 20 25 30 35 40 0 40 80 Current Amps Ambient Temperature C CS1 025 50 40 15 60 50 18 70 60 20 10 20 30 40 50 60 70 80 0 40 80 Current Amps Ambient Temperature C CS1 040 CS1 050 CS1 060 75 75 30 90 90 50 120 120 90 20 40 60 80 100 120 140 0 40 80 Current Amps Ambient Temperature C CS1 075 CS1 090 CS1 ...

Page 3: ...ring method for DC alarms only Jumper Terminals 4 6 Control Signal Input 24 VDC 6 32 VDC Alarm Output Solid State Switch Alarm Option Code 1 or 2 See Order Table 5 OPTIONAL ALARM WIRING continued 24 Vdc Control Signal Input Digital Logic 24 Vdc PNP Output Note Parallel connection required for multiple CS1 with Normally Open Alarm Switch Code 3 Single connection for CS1 with Normally Closed Alarm S...

Page 4: ...C DC power supply b Ratings Imax 150 mA Vmax 30 VAC DC Z close 15 ȍ impedance Z open 1 Mȍ impedance 2 Digital Logic PNP output signal for logic gated devices such as PLCs a Requires external 24VDC 6 32 VDC power supply b Ratings Imax 150 mA Vmax 30 VAC DC Alarm Behavior The functionality of the alarm switching varies depending on the type of gating signal For Models with 24 VDC Input Control Signa...

Reviews: