A–17
Configuration Record Forms: Appendix – A
VOLTAGE RELAY
VOLT curr freq pwr
27 PHASE UNDERVOLTAGE
PHASE_UNDER phase_over
27 #1 PICKUP
108 Volts
27 #1 DELAY
30 Cycles
59 PHASE OVERVOLTAGE
phase_under PHASE_OVER
59 #1 PICKUP
132 Volts
59 #1 DELAY
30 Cycles
27G NEUTRAL UNDERVOLTAGE
NUTRL_UNDER nutrl_over
FUNCTION(S) DISABLED
SEE CONFIGURE MENU
59G NEUTRAL OVERVOLTAGE
nutrl_under NUTRL_OVER
FUNCTION(S) DISABLED
SEE CONFIGURE MENU
47 NEG SEQ OVERVOLTAGE
NEG_SEQ peak_over
FUNCTION(S) DISABLED
SEE CONFIGURE MENU
59I PEAK OVERVOLTAGE
neg_seq PEAK_OVER
FUNCTION(S) DISABLED
SEE CONFIGURE MENU
Figure A-7
Setpoint & Timing – As Shipped (1 of 2)
CURRENT RELAY
volt CURR freq pwr
50 INST OVERCURRENT
INST inv
FUNCTION(S) DISABLED
SEE CONFIGURE MENU
51V INV TIME OVERCURRENT
inst INV
FUNCTION(S) DISABLED
SEE CONFIGURE MENU
50G INST OVERCURRENT
NUTRL_INST nutrl_inv
FUNCTION(S) DISABLED
SEE CONFIGURE MENU
51G INV TIME OVERCURRENT
nutrl_inst NUTRL_INV
FUNCTION(S) DISABLED
SEE CONFIGURE MENU
46 NEG SEQ OVERCURRENT
NEG_SEQ dir n_dir
FUNCTION(S) DISABLED
SEE CONFIGURE MENU
67 DIR OVERCURRENT
neg_seq DIR n_dir
FUNCTION(S) DISABLED
SEE CONFIGURE MENU
67N DIR NEUTRAL OVERCURR
neg_seq dir N_DIR
FUNCTION(S) DISABLED
SEE CONFIGURE MENU
NEUTRAL DIR SETUP
N_DIRSU
FUNCTION(S) DISABLED
SEE CONFIGURE MENU
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...