2–40
M-3520 Instruction Book
@ : WARNING, Function DISABLED until output selected!
(67N) - RESIDUAL DIRECTIONAL OVERCURRENT
Save
Cancel
Def. Time
OUTPUT
8
7
6
5
4
3
2
1
FL
6
5
4
3
2
1
Blocking Input
@
Ground Directional Element:
Enable
Disable
Pickup:
Delay:
0.5 Amp
1 Cycle
240.0 Amps
8160 Cycles
Inv. Time
OUTPUT
8
7
6
5
4
3
2
1
FL
6
5
4
3
2
1
Blocking Input
@
Pickup:
Time Dial:
0.25 Amp
0.5
12.00 Amps
11.0
Curves
Definite Time
IECI
Inverse
IECVI
Very Inverse
IECEI
Extremely Inverse
IECLTI
Ground Directional Element:
Enable
Disable
Max Sensitivity:
Polarization:
0
o
359
o
Type 1 (Zero Sequence)
Type 3 (Negative Sequence)
Type 5, Dual (Type 1 or Type 4)
Type 2 (Vg)
Type 4 (
I
g)
Figure 2-28
M-3822 IPScom® for Windows™ Residual Directional Overcurrent (67N) Setpoint
Ranges
Path
: Relay Menu/Setup/Setpoints/(67N) Residual Directional Overcurrent
COMMAND BUTTONS
Save
Save
s all information to the relay.
Cancel
Returns the user to the previous window; any changes to the displayed information are lost.
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...