–7–
M-3520 Intertie Protection Relay
OPTIONAL FUNCTIONS
Device
Setpoint
Number
Function
Ranges
Increment
Accuracy
†
Phase Distance (dual–zone mho characteristic)
Phase Distance (dual–zone mho characteristic)
Phase Distance (dual–zone mho characteristic)
Phase Distance (dual–zone mho characteristic)
Phase Distance (dual–zone mho characteristic)
Circle Diameter #1, #2
0.1 to 100.0
Ω
0.1
Ω
&
0.1
Ω
or
&
5%
(0.5 to 500.0
Ω
)
(
&
0.5
Ω
or
&
5%)
Offset #1, #2
–100.0 to 100.0
Ω
0.1
Ω
&
0.1
Ω
or
&
5%
(–500.0 to 500.0
Ω
)
(
&
0.5
Ω
or
&
5%)
Impedance Angle #1, #2
0° to 90°
1°
&
1°
Time Delay #1, #2
1 to 8160 Cycles
1 Cycle
–1 to +3 Cycles or
&
1%
Out of Step (mho characteristic)
Out of Step (mho characteristic)
Out of Step (mho characteristic)
Out of Step (mho characteristic)
Out of Step (mho characteristic)
Circle Diameter
0.1 to 100.0
Ω
0.1
Ω
&
0.1
Ω
or 5%
(0.5 to 500.0
Ω
)
(
&
0.5
Ω
or 5%)
Offset
–100.0 to 100.0
Ω
0.1
Ω
&
0.1
Ω
or 5%
(–500.0 to 500.0
Ω
)
(
&
0.5
Ω
or 5%)
Impedance Angle
0° to 90°
1°
&
1°
Blinder
0.1 to 50.0
Ω
0.1
Ω
&
0.1
Ω
or 5%
(0.5 to 250.0
Ω
)
(
&
0.5
Ω
or 5%)
Time Delay
1 to 8160 Cycles
1 Cycle
&
1 Cycle or
&
1%
Trip on mho Exit
Enable/Disable
Pole Slip Counter
1 to 20
1
Pole Slip Reset
1 to 8160 Cycles
1 Cycle
&
1 Cycle or
&
1%
Rate of Change of Frequency
Rate of Change of Frequency
Rate of Change of Frequency
Rate of Change of Frequency
Rate of Change of Frequency
Pickup #1, #2
0.10 to 20.00 Hz/Sec
0.01 Hz/Sec
&
0.05 Hz/Sec or
&
5%
Time Delay #1, #2
1 to 8160 Cycles
1 Cycle
+20 Cycles
Negative Sequence
Voltage Inhibit
0 to 99%
1%
&
0.5%
Nominal Settings
Nominal Settings
Nominal Settings
Nominal Settings
Nominal Settings
Nominal Voltage
60 to 140 V
1 V
—
Nominal Current
0.5 to 6.00 A
0.01 A
—
VT Configuration
Line-Line
Line-Ground
Line-Ground to Line-Line*
Seal-In Delay
2 to 8160 Cycles
1 Cycle
–1 to +3 Cycles or
&
1%
*When line-ground to line-line is selected, the relay internally calculates the line-line voltage from the
line-ground voltages for all voltage-sensitive functions. This line-ground to line-line selection should only
be used to a VT nominal secondary voltage of 69 V (not 120 V).
78
†
Select the greater of these accuracy values.
Values in parentheses apply to 1 Amp CT secondary rating.
21
81R
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...