2–19
Application - 2
@ : WARNING, Function DISABLED until output selected!
(32) - REVERSE/FORWARD POWER
-3.000 p.u.
1 Cycle
3.000 p.u.
8160 Cycles
#1
OUTPUT
8
7
6
5
4
3
2
1
FL
6
5
4
3
2
1
Blocking Input
@
Overpower
Underpower
Three Phase Detection:
Enable
Disable
-3.000 p.u.
1 Cycle
3.000 p.u.
8160 Cycles
#1
OUTPUT
8
7
6
5
4
3
2
1
FL
6
5
4
3
2
1
Blocking Input
@
Overpower
Underpower
Three Phase Detection:
Enable
Disable
Save
Cancel
Pickup:
Delay:
Pickup:
Delay:
Figure 2-11
M-3822 IPScom
®
for Windows™ Directional Power (32) Setpoint Ranges
Path
: Relay Menu/Setup/Setpoints/(32) Directional Power
COMMAND BUTTONS
Save
Saves all information to the relay.
Cancel
Returns the user to the previous window; any changes to the displayed information are lost.
32 #1 PICKUP
________ PU
32 #1 OVER/UNDER POWER
over_power under_power
32 #1 DELAY
________ Cycles
32#1 THREE PHASE DETECT
disable ENABLE
32 #2 PICKUP
________ PU
32 #2 OVER/UNDER POWER
over_power under_power
32 #2 delay
________ Cycles
32 #2 THREE PHASE DETECT
disable ENABLE
If this function is enabled, the following settings are applicable
This screen present if VT configuration is set Line-to-Ground.
This screen present if VT configuration is set Line-to-Ground.
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...