Technical data
94
Automation PC 3100 User's manual V 1.00
Translation of the original documentation
2.3.5.10 5AC901.IETH-00
2.3.5.10.1 General information
Interface option 5AC901.IETH-00 is equipped with a 10/100/1000BASE-T Ethernet interface.
•
1x Ethernet interface 10/100/1000BASE-T
•
Compatible with APC910/PPC900 and APC3100/PPC3100
Interface option 5AC901.IETH-00 can only be operated in the IF option 2 slot.
2.3.5.10.2 Order data
Model number
Short description
Figure
Interface options
5AC901.IETH-00
Interface card - 1x ETH 10/100/1000 - For APC910/PPC900/
APC3100/PPC3100
Table 112: 5AC901.IETH-00 - Order data
2.3.5.10.3 Technical data
Information:
The following specified characteristic data, features and limit values are only valid for these individual
components and may differ from those of the complete system. The data specified for the complete
system applies to the complete system in which this individual component is used, for example.
Model number
5AC901.IETH-00
General information
B&R ID code
EC3C
Diagnostics
Data transfer
Yes, using LED status indicator
Certifications
CE
Yes
UL
cULus E115267
Industrial control equipment
DNV GL
Temperature:
B
(0 - 55°C)
Humidity:
B
(up to 100%)
Vibration:
A
(0.7 g)
EMC:
B
(Bridge and open deck)
1)
Interfaces
Ethernet
Quantity
1
Controller
Intel I210
Design
RJ45, shielded
Transfer rate
10/100/1000 Mbit/s
2)
Cable length
Max. 100 m between two stations (segment length)
Electrical characteristics
Power consumption
1 W
Operating conditions
Pollution degree per EN 61131-2
Pollution degree 2
Environmental conditions
Temperature
Operation
0 to 55°C
3)
Storage
-20 to 60°C
Transport
-20 to 60°C
Relative humidity
Operation
5 to 90%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Weight
Approx. 35 g
Table 113: 5AC901.IETH-00 - Technical data
1)
Yes, although applies only if all components installed in the complete system have this certification and are listed on the associated DNV GL certificate for
theproduct family.
2)
Switching takes place automatically.
3)
For detailed information, see the temperature tables in the user's manual.
StockCheck.com