Technical data
110
Automation PC 3100 User's manual V 1.00
Translation of the original documentation
Model number
5AC901.BUPS-00
Electrical characteristics
Nominal voltage
24 V
Capacity
4.5 Ah
Fuse
Yes
Battery charging data
Charging current
3)
Typ. 1 A
Operating conditions
Pollution degree per EN 61131-2
Pollution degree 2
Environmental conditions
Temperature
Operation
-30 to 60°C
4)
Storage
-65 to 80°C
Transport
-65 to 80°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Elevation
Operation
Max. 3000 m
Mechanical characteristics
Dimensions
Width
223.2 mm
Height
78.2 mm
Depth
145 mm
Weight
Approx. 4600 g
Table 138: 5AC901.BUPS-00 - Technical data
1)
Depends on the charging and discharging cycles (up to 80% battery capacity).
2)
Yes, but applies only if all components installed in the complete system have this certification and the complete system bears the corresponding mark.
3)
Maximum charging current.
4)
Battery backing is no longer provided if the temperature undershoots the minimum temperature or overshoots the maximum temperature. The battery is also
no longer charged since this can result in damage to the battery.
2.3.6.4.4 Service life
The following diagram shows the relationship between ambient temperature and service life.
20
35
45
55
65
75
85
50% reduction in service life expectancy if temperature increased by 8°C
Ambient temperature [°C]
Ye
ar
s
un
til
8
0%
o
f b
at
te
ry
c
ap
ac
ity
33°C
25
1
0
2
3
4
5
6
7
8
9
10
11
12
13
14
15
StockCheck.com