Appendix A: Configuration presets
92
1X-X3E Series Installation Manual
BS 7273 mode stage 2
Fire sounders cannot be manually activated. Fire sounders activated
intermittently during the sounders delay.
Table 39: Presets and zone characteristics
Preset
Zone description
Zone detection
13
Active EOL
Z1 and Z2 automatic, for extinguishing event
Z3 mixed, for fire detection
14
Active EOL, CleanMe
enabled
Z1 and Z2 automatic, for extinguishing event
Z3 mixed, for fire detection
Repeater with fire routing (EN 54-2)
All input/output supervision is disabled. No fire and extinguishing functionality.
Table 40: Presets and zone characteristics
Preset
Zone description
Zone detection
61
Not used
Not used
Repeater with fire routing (BS 7273)
All input/output supervision is disabled. No fire and extinguishing functionality.
Table 41: Presets and zone characteristics
Preset
Zone description
Zone detection
63
Not used
Not used
EN 54-13 supervision and Class A expansion board
outputs
Note:
The following presets are available for installations that use
EN 54-13 supervision (the SU setting is A). See “Supervision mode” on page 34
for more information.
Basic standard mode
Fire sounders cannot be manually activated in this operating mode (fire sounders
are only activated if there is a fire alarm).
The configured actuator delay is applied when the MCP Start is activated.
Table 42: Presets and zone characteristics
Preset
Zone description
Zone detection
01
EN 54-13 EOL
Z1 and Z2 automatic, for extinguishing event
Z3 mixed, for fire detection
Summary of Contents for 1 3E Series
Page 1: ...1X X3E Series Installation Manual P N 501 419303 1 20 ISS 20JUL21 ...
Page 86: ...Chapter 4 Maintenance 80 1X X3E Series Installation Manual ...
Page 106: ...Appendix A Configuration presets 100 1X X3E Series Installation Manual ...
Page 110: ...Appendix B Regulatory information 104 1X X3E Series Installation Manual ...
Page 113: ......
Page 114: ......