Chapter 3: Configuration and commissioning
1X-X3E Series Installation Manual
53
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
The internal buzzer and sounders sound for 5 seconds
when an alarm is activated in a zone test.
The internal buzzer and sounders do not sound when an
alarm is activated in a zone test.
Fire sounder re-sound
Use this menu to configure the sounder re-sound, on or off. This determines
sounder operation in a fire alarm event when sounders have been silenced by
pressing the Fire Sounder Start/Stop button and a new alarm event is reported in
a different zone. The default setting is On.
To configure the sounder re-sound:
1. Set the display as shown below, and then press Enter.
The Sounders Start/Stop LED flashes fast to indicate that the sounder re-
sound configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your change
The available settings for this feature are shown below.
Display
Description
The sounders re-sound if a new fire alarm event is
reported from a different zone.
The sounders do not re-sound if a new fire alarm event
is reported from a different zone.