Chapter 3: Configuration and commissioning
52
1X-X3E Series Installation Manual
Extinguishing agent flow
Use this menu to configure how the control panel enters into the extinguishing
released state: using extinguishing agent flow confirmation or immediately after
the activation of the actuator.
The default setting does not use extinguishing agent flow confirmation:
extinguishing agent flow OFF. Note that with this configuration the control panel
continues to provide indications of the extinguishing agent flow for information
purposes (wiring faults and activation).
If your installation requires an extinguishing agent flow signal, see “Connecting
an extinguishing agent flow device” on page 12 for more information.
To configure extinguishing agent flow:
1. Set the display as shown below, and then press Enter.
The red extinguishing agent flow LED flashes fast to indicate that the
configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
Extinguishing released after extinguishing agent flow
input activation.
Extinguishing released after actuator activation.
(Extinguishing agent flow indications available for
information purposes)
Fire sounder operation during a zone test
Use this menu to configure the sounder operation during a zone test. The default
setting for all operating modes is On.
To configure the sounder operation during a zone test:
1. Set the display as shown below, and then press Enter.
The Fire Sounders Start/Stop LED flashes fast to indicate that the sounder
operation during a zone test configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
Summary of Contents for 1 3E Series
Page 1: ...1X X3E Series Installation Manual P N 501 419303 1 20 ISS 20JUL21 ...
Page 86: ...Chapter 4 Maintenance 80 1X X3E Series Installation Manual ...
Page 106: ...Appendix A Configuration presets 100 1X X3E Series Installation Manual ...
Page 110: ...Appendix B Regulatory information 104 1X X3E Series Installation Manual ...
Page 113: ......
Page 114: ......