Chapter 3: Configuration and commissioning
1X-X3E Series Installation Manual
33
Basic default configuration
Use this menu to select operating mode configuration presets.
In both basic standard and basic evacuation modes, zone detection is the same.
The extinguishing area uses Z1 and Z2 (automatic). Fire detection uses Z3
(mixed).
Available presets are shown in the table below. The default setting is 01 (Basic
standard mode, passive end-of-line).
Table 14: Operating mode configuration presets
Display
Mode
Zone configuration Manual fire
sounder start
Actuator delay
for MCP Start
01 (default)
Basic standard
Passive end-of-line No
Yes
02
Basic standard
Passive end-of-line,
CleanMe enabled
No
Yes
05
Basic evacuation
Passive end-of-line Yes (operator
user level) [1]
No (bypassed)
06
Basic evacuation
Passive end-of-line,
CleanMe enabled
Yes (operator
user level) [1]
No (bypassed)
11
BS 7273 stage 1
Active EOL
No
Yes
12
BS 7273 stage 2
Active EOL
No
Yes
61
Repeater with fire
routing (EN 54-2)
N/A
N/A
N/A
63
Repeater with fire
routing (BS 7273)
N/A
N/A
N/A
00
Custom [2]
N/A
N/A
N/A
[1] A fire alarm is not required to activate the fire sounders.
[2] This option cannot be selected. It is displayed automatically when an advanced configuration
is entered
To change the operation mode configuration preset:
1. Set the display as shown below, and then press Enter.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
Summary of Contents for 1 3E Series
Page 1: ...1X X3E Series Installation Manual P N 501 419303 1 20 ISS 20JUL21 ...
Page 86: ...Chapter 4 Maintenance 80 1X X3E Series Installation Manual ...
Page 106: ...Appendix A Configuration presets 100 1X X3E Series Installation Manual ...
Page 110: ...Appendix B Regulatory information 104 1X X3E Series Installation Manual ...
Page 113: ......
Page 114: ......