Chapter 3: Configuration and commissioning
1X-X3E Series Installation Manual
45
Hold mode
Use this menu to set the operating mode for this device (mode A or B). The
default setting is mode A.
For a description of the emergency MCP Hold function and device, see
“Connecting extinguishing system manual call points” on page 11.
To configure the emergency hold device mode:
1. Set the display as shown below, and then press Enter.
The MCP Hold LED flashes fast to indicate that the configuration menu is
active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
Mode A: The actuator delay countdown continues during
MCP Hold activation.
Mode B: The actuator delay countdown restarts when
the MCP Hold device is restored. MCP Hold is indicated
using a specific sounder tone.
Activation tone
Use this menu to set the extinguishing activation tone of the extinguishing
sounders on the control panel PCB: continuous or pulsed. The pulsed pattern is
1 second on, 1 second off. The default setting is pulsed mode.
To configure the activation tone:
1. Set the display as shown below, and then press Enter.
The red Extinguishing Sounders LED flashes fast to indicate that the
configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
Summary of Contents for 1 3E Series
Page 1: ...1X X3E Series Installation Manual P N 501 419303 1 20 ISS 20JUL21 ...
Page 86: ...Chapter 4 Maintenance 80 1X X3E Series Installation Manual ...
Page 106: ...Appendix A Configuration presets 100 1X X3E Series Installation Manual ...
Page 110: ...Appendix B Regulatory information 104 1X X3E Series Installation Manual ...
Page 113: ......
Page 114: ......