Chapter 3: Configuration and commissioning
1X-X3E Series Installation Manual
39
Advanced configuration
The default password for advanced configuration is 4444. After entering the
password, the first displayed menu is the Advanced default configuration
(indicating advanced installer user level). For more information see “User level
passwords and indications” on page 27.
The advanced configuration menu
Configuration options for this menu are shown in the table below. More
information for each option is included in the related topic.
Table 15: The advanced configuration menu
Display
Menu
Values
Advanced default configuration
See Table 14 on page 33
EN 54-13 supervision
Of= EN54-13 supervision Off and class
B outputs
A= EN54-13 supervision On for zone
and class A expansion board outputs
Default: Off
Panel mode
Basic standard
Basic evacuation
BS 7273 mode stage 1
BS 7273 mode stage 2
Repeater with fire routing (EN 54-2)
Repeater with fire routing (BS 7273)
Custom
Actuator delay
00 to 60 seconds
Default: 10 seconds
Reset disabled delay
00 to 30 minutes
Default: 2 minutes
Safety door monitoring
ON/OFF
Default: Off
Safety door fault delay
10 to 90 seconds
Default: 30 seconds
Pressure switch type
Normally closed
Normally open
Default: Normally closed
Activation tone
Pulsed
Continuous
Default: Pulsed
Summary of Contents for 1 3E Series
Page 1: ...1X X3E Series Installation Manual P N 501 419303 1 20 ISS 20JUL21 ...
Page 86: ...Chapter 4 Maintenance 80 1X X3E Series Installation Manual ...
Page 106: ...Appendix A Configuration presets 100 1X X3E Series Installation Manual ...
Page 110: ...Appendix B Regulatory information 104 1X X3E Series Installation Manual ...
Page 113: ......
Page 114: ......